Plan Review Notes For Permit 13070174 |
Permit Number |
13070174 |
|
Review Stop |
B |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2013-12-11 16:23:56 | RESIDENTIAL (R3) GARAGE CONVERSION, FIFTH CHECKLIST. | | CODE: 2010 FBC. | | | | 1- ENGINEER TO USE CURRENT SEAL AS REQUIRED BY CHAPTER | | 471 FLORIDA STATUTE. SEAL THAT SAYS "CERTIFICATE" | | INSTEAD OF "LICENSE" IS NOT ALLOWED SINCE 2006. (REPEAT | | COMMENT). | | | | 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS TO FBC. | | (REPEAT COMMENT). | | | | 3- REVISE SHUTTER INSTALLATION SCHEDULE. CLEARLY | | SPECIFY MOUNTING CONDITION AT TOP AND BOTTOM TO VERIFY | | ANCHOR SPACING REQUIRED TO MEET THE DESIGN PRESSURES OF | | SEC. R301.1 OF 2010 FBC-RESIDENTIAL. (SEE SHEET 4 OF 7 | | AND 5 OF 7 OF DRAWINGS SUBMITTED). | | | | 4- ENERGY CALCULATIONS SUBMITTED: OWNER/AGENT TO | | CERTIFY AND DATE BOTTOM OF FORM AS REQUIRED BY SEC. | | 103.2.3.2 OF 2010 FBC-ENERGY CONSERVATION. | | | | 5- PROVIDE WINDOW AND DOOR MANUFACTURER'S | | SPECIFICATIONS SHOWING THE U-FACTOR AND SHGC FACTOR | | SPECIFIED ON THE ENERGY CALCULATIONS AS REQUIRED BY | | SEC. 405.4.3 OF 2010 FBC-ENERGY CONSERVATION. | | | | ***NOTE: | | INFORMATION SUBMITTED IS FOR PGT WINDOWS AND DOORS, BUT | | PRODUCT APPROVAL SUBMITTED IS FOR JELD-WEN DOORS AND | | WINDOWS. | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|