2013-11-25 18:58:02RESIDENTIAL (R3) GARAGE CONVERSION, FOURTH MECHANICAL
 REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS.
 COMPLETE CALCULATIONS NEED TO BE DONE BASED ON THE
 BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION OF THE
 BUILDING AS REQUIRED BY SEC. 403.6.1 OF 2010 FBC-ENERGY
 CONSERVATION. ALSO, NEED TO SHOW THE MANUFACTURER AND
 MODEL NUMBERS (INDOOR AND OUTDOOR).
  
 ***NOTE: EQUIPMENT TO MATCH EQUIPMENT LISTED ON
 DRAWINGS SUBMITTED.
  
 ***EQUIPMENT SHOWN ON THE CALCULATIONS DOESN'T MATCH
 PLANS SUBMITTED AND CALCULATIONS ARE NOT DONE BASED ON
 THE ORIENTATION OF THE BUILDING.
  
 B) CALCULATIONS FOR REPLACEMENT EQUIPMENT NEED TO BE
 DONE BY AN A/C CONTRACTOR OR LICENSED FLORIDA ENGINEER
 AS REQUIRED BY SEC. 101.4.7.1.2 OF 2010 FBC-ENERGY
 CONSERVATION. (REPEAT COMMENT).
  
 ****NOTE: THIS TO BE DONE ON A SEPARATE PERMIT. THIS
 PERMIT APPLICATION IS FOR THE GARAGE CONVERSION ONLY.
  
  
  
 2- BEDROOM TO SHOW COMPLIANCE WITH THE RETURN AIR AND
 BALANCED RETURN AIR REQUIREMENTS OF SEC. R1602 OF 2010
 FBC-RESIDENTIAL. (REPEAT COMMENT).
  
 3- EQUIPMENT LISTED ON THE A/C PLAN, EQUIPMENT LISTED
 ON THE EQUIPMENT SIZING CALCULATIONS AND INFORMATION ON
 THE ENERGY CALCULATIONS NEED TO MATCH. CHECK SIZE AND
 SEER, ETC. REVISE AS REQUIRED TO MATCH. SEC. 103.2.2 OF
 2010 FBC-ENERGY CONSERVATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712