2013-11-25 18:58:02 | RESIDENTIAL (R3) GARAGE CONVERSION, FOURTH MECHANICAL |
| REVIEW CHECKLIST. |
| CODE: 2010 FBC. |
| |
| 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS. |
| COMPLETE CALCULATIONS NEED TO BE DONE BASED ON THE |
| BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION OF THE |
| BUILDING AS REQUIRED BY SEC. 403.6.1 OF 2010 FBC-ENERGY |
| CONSERVATION. ALSO, NEED TO SHOW THE MANUFACTURER AND |
| MODEL NUMBERS (INDOOR AND OUTDOOR). |
| |
| ***NOTE: EQUIPMENT TO MATCH EQUIPMENT LISTED ON |
| DRAWINGS SUBMITTED. |
| |
| ***EQUIPMENT SHOWN ON THE CALCULATIONS DOESN'T MATCH |
| PLANS SUBMITTED AND CALCULATIONS ARE NOT DONE BASED ON |
| THE ORIENTATION OF THE BUILDING. |
| |
| B) CALCULATIONS FOR REPLACEMENT EQUIPMENT NEED TO BE |
| DONE BY AN A/C CONTRACTOR OR LICENSED FLORIDA ENGINEER |
| AS REQUIRED BY SEC. 101.4.7.1.2 OF 2010 FBC-ENERGY |
| CONSERVATION. (REPEAT COMMENT). |
| |
| ****NOTE: THIS TO BE DONE ON A SEPARATE PERMIT. THIS |
| PERMIT APPLICATION IS FOR THE GARAGE CONVERSION ONLY. |
| |
| |
| |
| 2- BEDROOM TO SHOW COMPLIANCE WITH THE RETURN AIR AND |
| BALANCED RETURN AIR REQUIREMENTS OF SEC. R1602 OF 2010 |
| FBC-RESIDENTIAL. (REPEAT COMMENT). |
| |
| 3- EQUIPMENT LISTED ON THE A/C PLAN, EQUIPMENT LISTED |
| ON THE EQUIPMENT SIZING CALCULATIONS AND INFORMATION ON |
| THE ENERGY CALCULATIONS NEED TO MATCH. CHECK SIZE AND |
| SEER, ETC. REVISE AS REQUIRED TO MATCH. SEC. 103.2.2 OF |
| 2010 FBC-ENERGY CONSERVATION. |
| |