2013-11-25 18:46:38RESIDENTIAL (R3) GARAGE CONVERSION, FOURTH BUILDING
 REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- ENGINEER TO USE CURRENT SEAL AS REQUIRED BY CHAPTER
 471 FLORIDA STATUTE. SEAL THAT SAYS "CERTIFICATE"
 INSTEAD OF "LICENSE" IS NOT ALLOWED SINCE 2006. (REPEAT
 COMMENT. THREE TIMES).
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) SINGLE HUNG WINDOWS THAT MEET THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER OF RECORD. DRAWINGS FOR
 FLORIDA PRODUCT APPROVAL FL 11120-R8 SUBMITTED DOESN'T
 MEET THE DESIGN PRESSURES SHOWN ON PLANS.
  
 ***NOTE: ENGINEER OF RECORD APPROVED THIS PRODUCT
 APPROVAL, BUT IT DOESN'T MEET THE DESIGN PRESSURES
 CALCULATED BY HIM.
  
 B) HURRICANE SHUTTERS. PROVIDE TWO CLEAR COPIES. SECOND
 COPY SUBMITTED IS NOT CLEAR. DRAWINGS ARE INCOMPLETE.
 (NOA 12-0320.26).
  
 C) FRENCH DOORS. PROVIDE TWO COPIES. SECOND COPY
 SUBMITTED IS NOT CLEAR. DRAWING S ARE INCOMPLETE. (NOA
 09-0608.16).
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL OF THE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS. (REPEAT COMMENT).
  
 4- REVISE SHUTTER INSTALLATION SCHEDULE. DESIGN
 PRESSURES TO MATCH THOSE SPECIFIED BY THE ENGINEER OF
 RECORD. AND, CLEARLY SPECIFY MOUNTING CONDITION AT TOP
 AND BOTTOM TO VERIFY ANCHOR SPACING REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS TO FBC.
  
 5- ENERGY CALCULATIONS SUBMITTED ARE DONE FOR THE
 ENTIRE HOUSE. INFORMATION SUBMITTED ON THE ENERGY
 CALCULATIONS WILL NEED TO BE VERIFIED IN THE FIELD.
 OTHERWISE, INSPECTIONS WILL BE FAILED. PROVIDE WINDOW
 AND DOOR SPECIFICATIONS SHOWING THE U-FACTOR AND SHGC
 FACTOR SPECIFIED ON THE ENERGY CALCULATIONS AND
 SPECIFICATIONS SHOWING HOW THE EXISTING HOUSE WALLS AND
 CEILING WILL MEET THE R-VALUE INSULATION SHOWN ON THE
 ENERGY CALCULATIONS.. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 6- TYPICAL WALL SECTION DETAIL WAS REVISED. THE R VALUE
 FOR THE WALL IS ONLY FOR THE R VALUE OF THE INSULATION
 INSTALLED. CONCRETE BLOCK SHALL NOT BE INCLUDED. SEC.
 304.1.2 OF 2010 FBC-ENERGY CONSERVATION. REVISE AS
 REQUIRED. NOTE: PLANS AND ENERGY CALCULATIONS NEED TO
 MATCH.
  
 7- PROVIDE MANUFACTURER CUT SHEETS FOR EGRESS WINDOW
 SIZE 36" X 50" SHOWN ON BEDROOM TO VERIFY COMPLIANCE
 WITH SEC. R310 OF 2010 FBC-RESIDENTIAL.
  