Plan Review Notes For Permit 13070174 |
Permit Number |
13070174 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2013-10-31 07:55:31 | COMMENTS FROM THE LAST REVIEW WERE NOT ADDRESSED | | | | 2010 FBC / 2008 NEC | | | | DENIED BY ELECTRIC | | | | 1) THE 150 AMP SUB-PANEL REQUIRES (3) #1/0 THW CU | | CONDUCTORS AND A #6 GROUND WIRE IN 1-1/2" CONDUIT. NEC | | TABLE 310.16, TABLE 250.66 AND ANNEX C TABLE C.1 | | | | 2) SHOW COMPLIANCE WITH NEC 250.94 FOR INTER-SYSTEM | | BONDING REQUIREMENT. | | | | 3) REVISE GENERAL ELECTRICAL NOTE THAT GFCI ARE | | REQUIRED WITHIN 6 FEET OF THE SINK. 2008 NEC 210.8 (A) | | (6) REQUIRES ALL RECEPTACLES INSTALLED TO SERVE KITCHEN | | COUNTER TOPS TO BE GFCI. | | | | 4) THE RECEPTACLE LOCATED IN THE ATTACHED UTILITY SHED | | IS REQUIRED TO BE GFCI PROTECTED. NEC 210.8 (A) (2) | | | | 5) SHOW COMPLIANCE WITH FBC 314 .3.1 FOR REQUIRED SMOKE | | ALARMS. | | | | 6) SHOW COMPLIANCE WITH NEC 210.52 (E) (1) FOR REQUIRED | | OUTDOOR OUTLETS AT THE FRONT AND BACK OF THE DWELLING. | | | | 7) PLEASE SEE BUILDING REVIEW COMMENTS REGARDING THE | | REQUIRED SEALS THAT ARE ACCEPTABLE TO THE BOARD OF | | FLORIDA ENGINEERS. FAC 61G15-23.001 & SECTION 471.025 | | F.S. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|