2013-09-26 16:30:36RESIDENTIAL (R3) GARAGE CONVERSION, SECOND MECHANICAL
 REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- A)PROVIDE EQUIPMENT SIZING CALCULATIONS SHOWING THE
 MANUFACTURER AND MODEL NUMBERS (INDOOR AND OUTDOOR) AS
 REQUIRED BY SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION.
 ***NOTE; EQUIPMENT TO MATCH EQUIPMENT LISTED ON
 DRAWINGS SUBMITTED.
  
 B) CALCULATIONS FOR REPLACEMENT EQUIPMENT NEED TO BE
 DONE BY AN A/C CONTRACTOR OR LICENSED FLORIDA ENGINEER
 AS REQUIRED BY SEC. 101.4.7.1.2 OF 2010 FBC-ENERGY
 CONSERVATION. (REPEAT COMMENT).
  
 2- PLANS TO SHOW COMPLIANCE WITH THE RETURN AIR AND
 BALANCED RETURN AIR REQUIREMENTS OF SEC. R1602 OF 2010
 FBC-RESIDENTIAL. (REPEAT COMMENT).
  
 3- PROVIDE DOCUMENTATION SHOWING HOW OBTAINING THE R
 VALUE AND U VALUES SHOWN FOR THE WALLS, WINDOWS, ETC.
 ON THE EQUIPMENT SIZING CALCULATIONS SUBMITTED. SEC.
 103.2.2 OF 2010 FBC-ENERGY CONSERVATIONS.
 ***NOTE: COORDINATE INFORMATION WITH PLANS AND ENERGY
 CALCULATIONS SUBMITTED.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
  
  