Plan Review Notes
Plan Review Notes For Permit 13070174
Permit Number 13070174
Review Stop E
Sequence Number 2
Notes
Date Text
2013-10-22 11:37:012010 FBC / 2008 NEC
  
 DENIED BY ELECTRIC
  
 1) THE 150 AMP SUB-PANEL REQUIRES (3) #1/0 THW CU
 CONDUCTORS AND A #6 GROUND WIRE IN 1-1/2" CONDUIT. NEC
 TABLE 310.16, TABLE 250.66 AND ANNEX C TABLE C.1
  
 2) SHOW COMPLIANCE WITH NEC 250.94 FOR INTER-SYSTEM
 BONDING REQUIREMENT.
  
 3) REVISE GENERAL ELECTRICAL NOTE THAT GFCI ARE
 REQUIRED WITHIN 6 FEET OF THE SINK. 2008 NEC 210.8 (A)
 (6) REQUIRES ALL RECEPTACLES INSTALLED TO SERVE KITCHEN
 COUNTER TOPS TO BE GFCI.
  
 4) THE RECEPTACLE LOCATED IN THE ATTACHED UTILITY SHED
 IS REQUIRED TO BE GFCI PROTECTED. NEC 210.8 (A) (2)
  
 5) SHOW COMPLIANCE WITH FBC 314 .3.1 FOR REQUIRED SMOKE
 ALARMS.
  
 6) SHOW COMPLIANCE WITH NEC 210.52 (E) (1) FOR REQUIRED
 OUTDOOR OUTLETS AT THE FRONT AND BACK OF THE DWELLING.
  
 7) PLEASE SEE BUILDING REVIEW COMMENTS REGARDING THE
 REQUIRED SEALS THAT ARE ACCEPTABLE TO THE BOARD OF
 FLORIDA ENGINEERS. FAC 61G15-23.001 & SECTION 471.025
 F.S.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
2013-09-26 11:20:52NEW DRAWINGS SUBMITTED. JG.