2013-09-26 11:12:30 | RESIDENTIAL (R3) GARAGE CONVERSION, SECOND BUILDING |
| REVIEW CHECKLIST. |
| CODE: 2010 FBC. |
| |
| 1- ENGINEER TO USE CURRENT SEAL AS REQUIRED BY CHAPTER |
| 471 FLORIDA STATUTE. SEAL THAT SAYS "CERTIFICATE" |
| INSTEAD OF "LICENSE" IS NOT ALLOWED SINCE 2006. AND, |
| CLARIFY WHY THERE IS AN EXPIRATION DATE OF 2/28/13 |
| BELOW THE ENGINEER'S LICENSE NUMBER?. (REPEAT COMMENT). |
| |
| 2- SPECIFY TYPE OF WINDOW ON BEDROOM TO VERIFY |
| COMPLIANCE WITH EGRESS REQUIREMENTS. SEC. R310 OF 2010 |
| FBC-RESIDENTIAL. |
| ***COMMENTS TO RESPONSE: |
| A)INFORMATION SUBMITTED DOESN'T SPECIFY TYPE OF WINDOW. |
| |
| B) PROVIDE MANUFACTURER SPECS SHOWING THAT THE 36" X |
| 50" SPECIFIED WINDOW MEETS THE EGRESS REQUIREMENTS. |
| NEED TO VERIFY MIN. CLEAR WIDTH, MIN. CLEAR HEIGHT AND |
| MIN. TOTAL CLEAR OPENING. |
| |
| 3- PROVIDE DETAILS AND SPECIFICATIONS SHOWING HOW |
| OBTAINING R-6 VALUE IN THE CONCRETE BLOCK WALLS. |
| ***COMMENTS TO RESPONSE: |
| TYPICAL WALL DETAIL SUBMITTED SHOWS "REFLECTIX FOIL |
| INSUL. R-3.79". THIS DOESN'T MEET THE R-6 VALUE. NEED |
| TO USE ONLY THE R-VALUE OF THE INSTALLED INSULATION. |
| SEC. 304.1.2 OF 2010 FBC-ENERGY CONSERVATION. |
| |
| 4- ENERGY CALCULATIONS SUBMITTED; |
| A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING THE BUILDER'S NAME AND OWNER'S NAME. (SEC. |
| 103.2.1.1.2 OF 2010 FBC-ENERGY CONSERVATION. |
| |
| B) REVISE ROOF TYPE ON PAGE 3 OF 6 TO ADD THE FLAT ROOF |
| AREA OF THE ADDITION. SEC. 103.2.2 OF 2010 FBC-ENERGY |
| CONSERVATION. |
| |
| 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9N-3 FOR: |
| A) WINDOWS SHOWN ON PLANS. (REPEAT COMMENT. NO |
| SUBMITTED). |
| ***NOTE: PLEASE MAKE SURE PRODUCT APPROVAL MEETS THE |
| CALCULATED DESIGN PRESSURES. |
| |
| B) HURRICANE SHUTTERS IF WINDOWS DON'T HAVE HURRICANE |
| IMPACT GLAZING AND FOR FRENCH DOORS (FRENCH DOORS NOA |
| 09-0608.16 SUBMITTED IS FOR NON-IMPACT DOOR). |
| ***COMMENTS TO RESPONSE: NOA 09-0114.02 SUBMITTED WAS |
| CLOSED BY MIAMI-DADE. NEED CURRENT NOA. |
| |
| C) FRENCH DOORS THAT MEET THE DESIGN PRESSURES |
| CALCULATED BY THE ENGINEER OF RECORD. NOA 09-0415.08 |
| SUBMITTED DOESN'T MEET THOSE DESIGN PRESSURES. |
| |
| 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL OF THE ABOVE PRODUCT |
| APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY |
| AMENDMENTS. |
| |
| 7- REVISE THE HURRICANE SHUTTERS INSTALLATION SCHEDULE. |
| COORDINATE WITH NEW PRODUCT APPROVAL SUBMITTED. SEE |
| ITEM #5(B) ABOVE. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 8- PROVIDE MANUFACTURER'S INFORMATION FOR DOORS AND |
| WINDOWS U-FACTOR AND SHGC FACTOR AS SPECIFIED ON ITEM |
| #7 OF THE ENERGY CALCULATIONS SUBMITTED. SEC. 103.2.2 |
| OF 2010 FBC-ENERGY CONSERVATION. (REPEAT COMMENT. NOT |
| ADDRESSED). |
| |
| |
| *** PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO HELP EXPEDITE THE REVIEW PROCESS... |
| |
| |