Plan Review Notes
Plan Review Notes For Permit 13070174
Permit Number 13070174
Review Stop B
Sequence Number 2
Notes
Date Text
2013-09-26 11:12:30RESIDENTIAL (R3) GARAGE CONVERSION, SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- ENGINEER TO USE CURRENT SEAL AS REQUIRED BY CHAPTER
 471 FLORIDA STATUTE. SEAL THAT SAYS "CERTIFICATE"
 INSTEAD OF "LICENSE" IS NOT ALLOWED SINCE 2006. AND,
 CLARIFY WHY THERE IS AN EXPIRATION DATE OF 2/28/13
 BELOW THE ENGINEER'S LICENSE NUMBER?. (REPEAT COMMENT).
  
 2- SPECIFY TYPE OF WINDOW ON BEDROOM TO VERIFY
 COMPLIANCE WITH EGRESS REQUIREMENTS. SEC. R310 OF 2010
 FBC-RESIDENTIAL.
 ***COMMENTS TO RESPONSE:
 A)INFORMATION SUBMITTED DOESN'T SPECIFY TYPE OF WINDOW.
  
 B) PROVIDE MANUFACTURER SPECS SHOWING THAT THE 36" X
 50" SPECIFIED WINDOW MEETS THE EGRESS REQUIREMENTS.
 NEED TO VERIFY MIN. CLEAR WIDTH, MIN. CLEAR HEIGHT AND
 MIN. TOTAL CLEAR OPENING.
  
 3- PROVIDE DETAILS AND SPECIFICATIONS SHOWING HOW
 OBTAINING R-6 VALUE IN THE CONCRETE BLOCK WALLS.
 ***COMMENTS TO RESPONSE:
 TYPICAL WALL DETAIL SUBMITTED SHOWS "REFLECTIX FOIL
 INSUL. R-3.79". THIS DOESN'T MEET THE R-6 VALUE. NEED
 TO USE ONLY THE R-VALUE OF THE INSTALLED INSULATION.
 SEC. 304.1.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 4- ENERGY CALCULATIONS SUBMITTED;
 A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE BUILDER'S NAME AND OWNER'S NAME. (SEC.
 103.2.1.1.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 B) REVISE ROOF TYPE ON PAGE 3 OF 6 TO ADD THE FLAT ROOF
 AREA OF THE ADDITION. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) WINDOWS SHOWN ON PLANS. (REPEAT COMMENT. NO
 SUBMITTED).
 ***NOTE: PLEASE MAKE SURE PRODUCT APPROVAL MEETS THE
 CALCULATED DESIGN PRESSURES.
  
 B) HURRICANE SHUTTERS IF WINDOWS DON'T HAVE HURRICANE
 IMPACT GLAZING AND FOR FRENCH DOORS (FRENCH DOORS NOA
 09-0608.16 SUBMITTED IS FOR NON-IMPACT DOOR).
 ***COMMENTS TO RESPONSE: NOA 09-0114.02 SUBMITTED WAS
 CLOSED BY MIAMI-DADE. NEED CURRENT NOA.
  
 C) FRENCH DOORS THAT MEET THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER OF RECORD. NOA 09-0415.08
 SUBMITTED DOESN'T MEET THOSE DESIGN PRESSURES.
  
 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL OF THE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 7- REVISE THE HURRICANE SHUTTERS INSTALLATION SCHEDULE.
 COORDINATE WITH NEW PRODUCT APPROVAL SUBMITTED. SEE
 ITEM #5(B) ABOVE. SEC. 107.2.1 CITY AMENDMENTS.
  
 8- PROVIDE MANUFACTURER'S INFORMATION FOR DOORS AND
 WINDOWS U-FACTOR AND SHGC FACTOR AS SPECIFIED ON ITEM
 #7 OF THE ENERGY CALCULATIONS SUBMITTED. SEC. 103.2.2
 OF 2010 FBC-ENERGY CONSERVATION. (REPEAT COMMENT. NOT
 ADDRESSED).
  
  
 *** PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS...
  
  