2013-08-01 12:02:48RESIDENTIAL (R3) GARAGE CONVERSION, MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- REVISE EQUIPMENT SIZING CALCULATIONS SUBMITTED (SEC.
 403.6 OF 2010 FBC-ENERGY CONSERVATION) :
 A) DESIGN CONDITIONS TO COMPLY WITH SEC. 302.1 OF 2010
 FBC-ENERGY CONSERVATION.
  
 B) SPECIFY OUTDOOR AND INDOOR UNITS (MODEL AND
 MANUFACTURER) SEC. 403.6.1 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 2 PROVIDE COMPLETE A/C PLANS. SHOW EQUIPMENT SPECIFIED
 ON THE EQUIPMENT SIZING CALCULATIONS, ALL DUCTWORK
 LOCATION AND SIZES, EQUIPMENT LOCATION, ETC. SEC.
 107.3.5.3 (10) OF CITY AMENDMENTS TO FBC.
  
 3- PLANS TO SHOW COMPLIANCE WITH THE RETURN AIR AND
 BALANCED RETURN AIR REQUIREMENTS OF SEC. R1602 OF 2010
 FBC-RESIDENTIAL.
  
 4- HOW GETTING R-15 VALUE ON CONCRETE BLOCK WALLS, AND
 R-30 IN CEILING ON A FLAT ROOF AS SHOWN ON THE
 EQUIPMENT SIZING CALCULATIONS. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 5- CLARIFY IF CALCULATIONS ARE FOR THE CONVERTED GARAGE
 AREA ONLY OR FOR ENTIRE HOUSE. IF CHANGING THE A/C SIZE
 FOR ENTIRE HOUSE, THEN THE CALCULATIONS NEED TO TAKE
 INTO CONSIDERATION THE WHOLE HOUSE NOT JUST THE GARAGE
 AREA. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 6- COORDINATE EQUIPMENT SIZING CALCULATIONS WITH THE
 ENERGY CALCULATIONS. SEC. 107.2.1 CITY AMENDMENTS TO
 FBC.
  