Plan Review Notes
Plan Review Notes For Permit 13070172
Permit Number 13070172
Review Stop P
Sequence Number 1
Notes
Date Text
2013-07-25 17:54:14NEW SINGLE FAMILY RESIDENCE (R3), PLUMBING REVIEW
 COMMENTS.
 CODE: 2010 FBC-RESIDENTIAL.
  
 1- UPDATE ALL PLUMBING SPECIFICATIONS AND NOTES ON
 SHEET P-100 TO REFER TO THE CURRENT CODE 2010
 FBC-RESIDENTIAL.
  
 2- CLEANOUTS ARE REQUIRED AT THE BASE OF EACH WASTE
 STACK. SEC. P3005.2.6 OF 2010 FBC-RESIDENTIAL.
  
 3- WATER HEATER LOCATION DOESN'T COMPLY WITH SEC.
 P2801.3 OF 2010 FBC-RESIDENTIAL. NEED MIN. 30" SPACE IN
 FRONT OF THE WATER HEATER.
  
 4- MISSING CLOTHES WASHER ON THE PLUMBING SCHEDULE AND
 MISSING CLOTHES WASHER DRAINAGE PIPE SIZE ON THE
 PLUMBING RISER DIAGRAM. SEC. 107.2.1 CITY AMENDMENTS TO
 FBC.
  