Plan Review Notes For Permit 13070172 |
Permit Number |
13070172 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-07-25 17:43:20 | NEW SINGLE FAMILY RESIDENCE (R3), MECHANICAL REVIEW | | COMMENTS. | | CODE: 2010 FBC. | | | | 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS AS | | REQUIRED BY SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION. | | ***NOTE: COORDINATE WITH EQUIPMENT INFORMATION SHOWN ON | | A/C PLANS. | | | | 2- SHEET M-200. AIR HANDLER #1: RETURN AIR CAN'T BE | | TAKEN FROM THE KITCHEN. SEC. M1602.2(4) OF 2010 | | FBC-RESIDENTIAL. | | | | 3- SHEET M-201. RETURN AIR CAN'T BE FROM THE LAUNDRY | | ROOM. SEC. M1602.4 OF 2010 FBC-RESIDENTIAL. | | | | 4- LOCATION OF AIR HANDLER #2 DOESN'T COMPLY WITH SEC. | | M1305.1. NEED 30" MIN. WORKING SPACE IN FRONT OF UNIT. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|