2013-07-25 17:43:20NEW SINGLE FAMILY RESIDENCE (R3), MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS AS
 REQUIRED BY SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION.
 ***NOTE: COORDINATE WITH EQUIPMENT INFORMATION SHOWN ON
 A/C PLANS.
  
 2- SHEET M-200. AIR HANDLER #1: RETURN AIR CAN'T BE
 TAKEN FROM THE KITCHEN. SEC. M1602.2(4) OF 2010
 FBC-RESIDENTIAL.
  
 3- SHEET M-201. RETURN AIR CAN'T BE FROM THE LAUNDRY
 ROOM. SEC. M1602.4 OF 2010 FBC-RESIDENTIAL.
  
 4- LOCATION OF AIR HANDLER #2 DOESN'T COMPLY WITH SEC.
 M1305.1. NEED 30" MIN. WORKING SPACE IN FRONT OF UNIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712