2013-07-24 18:05:49 | NEW SINGLE FAMILY RESIDENCE (R3), BUILDING REVIEW |
| COMMENTS. |
| CODE: 2010 FBC. |
| |
| 1- PROVIDE SOIL TEST REPORT (2 COPIES). SEC. R401.4 OF |
| 2010 FBC-RESIDENTIAL. |
| |
| 2- ARCHITECTURAL PLANS ARE MISSING ALL DIMENSIONS. SEC. |
| 107.2.1 CITY AMENDMENTS TO FBC. |
| |
| 3- PROVIDE DRAINAGE PLAN. SEC. R401.3 OF 2010 |
| FBC-RESIDENTIAL. |
| |
| 4- ENERGY CALCULATIONS SUBMITTED. ALL THE INFORMATION |
| NEED TO BE COORDINATED WITH THE ARCHITECTURAL PLANS AND |
| PRODUCT APPROVALS SUBMITTED (SEC. 107.2.1 CITY |
| AMENDMENTS TO FBC): |
| A) ENGINEER PREPARING THE CALCULATIONS TO SIGN AND SEAL |
| FORM AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE. |
| |
| B) COMPLETE ALL THE INFORMATION ON TOP OF FORM. ALSO, |
| REVISE THE NAME OF BUILDER. |
| |
| C) REVISE CEILING AREA. SEE SEC. 402.2.13 OF 2010 |
| FBC-ENERGY CONSERVATION. |
| |
| D) REVISE THE AREA WEIGHTED AVERAGE OVERHANG DEPTH AND |
| AREA WEIGHTED AVERAGE SHGC. SEE PLANS AND REVISE AS |
| REQUIRED. |
| |
| E) REVISED RAISED FLOOR. (THERE IS NOT RAISED FLOOR). |
| SEE SEC. 402.2.12 OF 2010 FBC-ENERGY CONSERVATION. AND |
| WHERE IS OTHER FLOOR MENTIONED ON ITEM #8(C)? |
| |
| F) PLANS ARE DESIGNED WITH UNVENTED ATTIC. |
| |
| G) REVISE ROOF INFORMATION, WALLS INFORMATION, DOORS |
| INFORMATION, WINDOWS INFORMATION AND MECHANICAL |
| INFORMATION TO MATCH ARCHITECTURAL PLANS AND PRODUCT |
| APPROVALS SUBMITTED. |
| |
| H) COORDINATE ENERGY CALCULATIONS WITH THE A/C |
| EQUIPMENT SIZING CALCULATIONS. SEC. 403.6 FBC-ENERGY |
| CONSERVATION. |
| |
| 5- ARCHITECTURAL PLANS: A) TO SHOW HOW PROVIDING THE R |
| VALUE FOR THE CEILING (R30. SEE ICYNENE SPECS), WALLS |
| (R-7) AND FLOORS AS REQUIRED BY THE ENERGY |
| CALCULATIONS. SEC. 103 OF 2010 FBC-ENERGY CONSERVATION. |
| |
| B) TO SHOW CEILING FANS SIZES AND LOCATION SINCE ENERGY |
| CALCULATIONS ARE TAKING THE CEILING FANS CREDIT. SEE |
| TABLE 405.6.6 OF 2010 FBC-ENERGY CONSERVATION. |
| |
| 6- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| COUNTY FOR IMPACT FEES. BRING BACK STAMPED PLANS AND |
| COPY OF PAID RECEIPT. REQUIRED BY COUNTY IMPACT FEE |
| ORDINANCE. |
| |
| 7- ARCHITECTURAL PLANS NEED THE ARCHITECT'S LICENSE |
| NUMBER IN THE TITLE BLOCK. CHAPTER 481 FLORIDA STATUTE |
| AND SEC. 61G1-16.004. |
| |
| 8- PROVIDE MANUFACTURER'S SPECS FOR CHIMNEY AND |
| FIREPLACE. SEC. R1004 AND R1005. AND, PROVIDE |
| MANUFACTURER SPECIFICATIONS THAT ALLOW A CHIMNEY CAP AS |
| SHOWN ON PLANS. ARCHITECTURAL PLANS TO PROVIDE COMPLETE |
| SPECS AND DIMENSIONS FOR CHIMNEY CAP TO SHOW COMPLIANCE |
| WITH THE MANUFACTURER REQUIREMENTS. SEC. 107.2.1.3 CITY |
| AMENDMENTS. |
| |
| 9- PROVIDE PRODUCT APPROVAL (2COPIES) AS REQUIRED BY |
| DCA RULE 9N-3 FOR: |
| A) INSWING ENTRY DOOR SIZE AND TYPE AS SHOWN ON PLANS. |
| |
| B) TRANSOM AND MULLIONS ABOVE FRENCH DOORS AS SHOWN ON |
| PLANS. |
| |
| C) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| |
| D) ALL USP (SEE DETAIL 01/S-3) AND SIMPSON STRUCTURAL |
| CONNECTORS SPECIFIED ON ALL DETAILS, SECTIONS, TRUSS |
| ANCHOR SCHEDULE AND CONNECTOR SCHEDULE SPECIFIED ON |
| PLANS. NOTE: FLORIDA PRODUCT APPROVALS LISTED ON THE |
| TRUS ANCHOR SCHEDULE AND CONNECTOR'S SCHEDULE NEED TO |
| BE UPDATED TO 2010 FBC NUMBERS. AND, SPECIFY THE |
| FLORIDA PRODUCT APPROVAL NUMBER FOR ALL OTHER |
| CONNECTORS SPECIFIED ON ALL DETAILS IF NOT LISTED ON |
| THE CONNECTOR SCHEDULE. |
| |
| E) ARCHED CASEMENT WINDOWS WITH SIZE AS SPECIFIED ON |
| THE WINDOW SCHEDULE. |
| |
| F) ROOF TILE THAT IS DESIGNED FOR A 2:12 ROOF PITCH AS |
| SHOWN ON PLANS. |
| |
| G) ROOF TILE ADHESIVE, IF USING ADHESIVE FOR THE TILE |
| INSTALLATION. SEE TILE PRODUCT APPROVAL FOR LISTED |
| ADHESIVES. NEED TO MEET THE CALCULATED UPLIFT LOADS. |
| |
| H) GARAGE DOOR THAT MEETS THE DESIGN PRESSURES |
| CALCULATED BY THE ENGINEER OF RECORD. |
| |
| I) SHUTTERS AS SHOWN ON PLANS. AND PROVIDE COMPLETE |
| INSTALLATION SCHEDULE. |
| |
| J) ARCHITECT TO UPDATE THE NOA NUMBER FOR THE FRENCH |
| DOORS SHOWN ON THE DOOR SCHEDULE TO MATCH ACTUAL NOA |
| SUBMITTED. |
| |
| 10- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 11- SPECIFY ATTIC ACCESS SIZE AND LOCATION FOR MAIN |
| HOUSE AND GARAGE. SEC. R807. |
| |
| 12- PROVIDE COMPLETE SPECIFICATIONS AND DETAILS FOR THE |
| STAIRWAY, RAILINGS AND GUARDRAILS TO SHOW COMPLIANCE |
| WITH SEC. R311.7 AND R312 AND TABLE R301.5. |
| |
| 13- ARCHITECT TO SPECIFY ROOF TILE ATTACHMENT AS |
| REQUIRED BY SEC. 107.2.1.2 TO VERIFY COMPLIANCE WITH |
| THE CALCULATED DESIGN PRESSURES ON SHEET S-0. |
| |
| 14- SHEET S-0: COMPONENTS & CLADDING DIAGRAM "A" IS |
| MISSING ROOF ZONE 3. SEE FIGURE R301.2(7). |
| |
| 15- ARCHITECT TO SPECIFY GUTTERS AND DOWNSPOUTS AS |
| REQUIRED BY SEC. R318.6 (SPECIFY SIZE AND LOCATION). |
| |
| 16- SHEET S-5: MISSING DETAIL AND SPECS FOR LEDGER #3. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 17- ARCHITECTURAL SECTIONS AND WALL SECTIONS ARE |
| MISSING THE FLASHING SPECIFICATIONS. SEC. R703.8. |
| |
| 18- SHEET A-400 WINDOW AND DOOR SCHEDULE: UPDATE THE |
| MATERIAL TYPE AND GLAZING TO MATCH PRODUCT APPROVALS |
| SUBMITTED AND COORDINATE WITH SPECIFICATIONS ON THE |
| ENERGY CALCULATIONS. SEC. 103.2.2 OF 2010 FBC-ENERGY |
| CONSERVATION. |
| |
| ***PLEASE PROVIDE WRITTEN RESPONSE TO EACH COMMENT TO |
| EXPEDITE THE REVIEW PROCESS. |
| |
| ***NOTE: FOR YOUR INFORMATION. HOUSE DEMOLITION PERMIT |
| IS REQUIRED FOR THE DEMOLITION OF EXISTING HOUSE. |
| PERMIT IS NOT ISSUED YET. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561)805-6712 |
| |