2013-07-24 18:05:49NEW SINGLE FAMILY RESIDENCE (R3), BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE SOIL TEST REPORT (2 COPIES). SEC. R401.4 OF
 2010 FBC-RESIDENTIAL.
  
 2- ARCHITECTURAL PLANS ARE MISSING ALL DIMENSIONS. SEC.
 107.2.1 CITY AMENDMENTS TO FBC.
  
 3- PROVIDE DRAINAGE PLAN. SEC. R401.3 OF 2010
 FBC-RESIDENTIAL.
  
 4- ENERGY CALCULATIONS SUBMITTED. ALL THE INFORMATION
 NEED TO BE COORDINATED WITH THE ARCHITECTURAL PLANS AND
 PRODUCT APPROVALS SUBMITTED (SEC. 107.2.1 CITY
 AMENDMENTS TO FBC):
 A) ENGINEER PREPARING THE CALCULATIONS TO SIGN AND SEAL
 FORM AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE.
  
 B) COMPLETE ALL THE INFORMATION ON TOP OF FORM. ALSO,
 REVISE THE NAME OF BUILDER.
  
 C) REVISE CEILING AREA. SEE SEC. 402.2.13 OF 2010
 FBC-ENERGY CONSERVATION.
  
 D) REVISE THE AREA WEIGHTED AVERAGE OVERHANG DEPTH AND
 AREA WEIGHTED AVERAGE SHGC. SEE PLANS AND REVISE AS
 REQUIRED.
  
 E) REVISED RAISED FLOOR. (THERE IS NOT RAISED FLOOR).
 SEE SEC. 402.2.12 OF 2010 FBC-ENERGY CONSERVATION. AND
 WHERE IS OTHER FLOOR MENTIONED ON ITEM #8(C)?
  
 F) PLANS ARE DESIGNED WITH UNVENTED ATTIC.
  
 G) REVISE ROOF INFORMATION, WALLS INFORMATION, DOORS
 INFORMATION, WINDOWS INFORMATION AND MECHANICAL
 INFORMATION TO MATCH ARCHITECTURAL PLANS AND PRODUCT
 APPROVALS SUBMITTED.
  
 H) COORDINATE ENERGY CALCULATIONS WITH THE A/C
 EQUIPMENT SIZING CALCULATIONS. SEC. 403.6 FBC-ENERGY
 CONSERVATION.
  
 5- ARCHITECTURAL PLANS: A) TO SHOW HOW PROVIDING THE R
 VALUE FOR THE CEILING (R30. SEE ICYNENE SPECS), WALLS
 (R-7) AND FLOORS AS REQUIRED BY THE ENERGY
 CALCULATIONS. SEC. 103 OF 2010 FBC-ENERGY CONSERVATION.
  
 B) TO SHOW CEILING FANS SIZES AND LOCATION SINCE ENERGY
 CALCULATIONS ARE TAKING THE CEILING FANS CREDIT. SEE
 TABLE 405.6.6 OF 2010 FBC-ENERGY CONSERVATION.
  
 6- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY FOR IMPACT FEES. BRING BACK STAMPED PLANS AND
 COPY OF PAID RECEIPT. REQUIRED BY COUNTY IMPACT FEE
 ORDINANCE.
  
 7- ARCHITECTURAL PLANS NEED THE ARCHITECT'S LICENSE
 NUMBER IN THE TITLE BLOCK. CHAPTER 481 FLORIDA STATUTE
 AND SEC. 61G1-16.004.
  
 8- PROVIDE MANUFACTURER'S SPECS FOR CHIMNEY AND
 FIREPLACE. SEC. R1004 AND R1005. AND, PROVIDE
 MANUFACTURER SPECIFICATIONS THAT ALLOW A CHIMNEY CAP AS
 SHOWN ON PLANS. ARCHITECTURAL PLANS TO PROVIDE COMPLETE
 SPECS AND DIMENSIONS FOR CHIMNEY CAP TO SHOW COMPLIANCE
 WITH THE MANUFACTURER REQUIREMENTS. SEC. 107.2.1.3 CITY
 AMENDMENTS.
  
 9- PROVIDE PRODUCT APPROVAL (2COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) INSWING ENTRY DOOR SIZE AND TYPE AS SHOWN ON PLANS.
  
 B) TRANSOM AND MULLIONS ABOVE FRENCH DOORS AS SHOWN ON
 PLANS.
  
 C) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 D) ALL USP (SEE DETAIL 01/S-3) AND SIMPSON STRUCTURAL
 CONNECTORS SPECIFIED ON ALL DETAILS, SECTIONS, TRUSS
 ANCHOR SCHEDULE AND CONNECTOR SCHEDULE SPECIFIED ON
 PLANS. NOTE: FLORIDA PRODUCT APPROVALS LISTED ON THE
 TRUS ANCHOR SCHEDULE AND CONNECTOR'S SCHEDULE NEED TO
 BE UPDATED TO 2010 FBC NUMBERS. AND, SPECIFY THE
 FLORIDA PRODUCT APPROVAL NUMBER FOR ALL OTHER
 CONNECTORS SPECIFIED ON ALL DETAILS IF NOT LISTED ON
 THE CONNECTOR SCHEDULE.
  
 E) ARCHED CASEMENT WINDOWS WITH SIZE AS SPECIFIED ON
 THE WINDOW SCHEDULE.
  
 F) ROOF TILE THAT IS DESIGNED FOR A 2:12 ROOF PITCH AS
 SHOWN ON PLANS.
  
 G) ROOF TILE ADHESIVE, IF USING ADHESIVE FOR THE TILE
 INSTALLATION. SEE TILE PRODUCT APPROVAL FOR LISTED
 ADHESIVES. NEED TO MEET THE CALCULATED UPLIFT LOADS.
  
 H) GARAGE DOOR THAT MEETS THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER OF RECORD.
  
 I) SHUTTERS AS SHOWN ON PLANS. AND PROVIDE COMPLETE
 INSTALLATION SCHEDULE.
  
 J) ARCHITECT TO UPDATE THE NOA NUMBER FOR THE FRENCH
 DOORS SHOWN ON THE DOOR SCHEDULE TO MATCH ACTUAL NOA
 SUBMITTED.
  
 10- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 11- SPECIFY ATTIC ACCESS SIZE AND LOCATION FOR MAIN
 HOUSE AND GARAGE. SEC. R807.
  
 12- PROVIDE COMPLETE SPECIFICATIONS AND DETAILS FOR THE
 STAIRWAY, RAILINGS AND GUARDRAILS TO SHOW COMPLIANCE
 WITH SEC. R311.7 AND R312 AND TABLE R301.5.
  
 13- ARCHITECT TO SPECIFY ROOF TILE ATTACHMENT AS
 REQUIRED BY SEC. 107.2.1.2 TO VERIFY COMPLIANCE WITH
 THE CALCULATED DESIGN PRESSURES ON SHEET S-0.
  
 14- SHEET S-0: COMPONENTS & CLADDING DIAGRAM "A" IS
 MISSING ROOF ZONE 3. SEE FIGURE R301.2(7).
  
 15- ARCHITECT TO SPECIFY GUTTERS AND DOWNSPOUTS AS
 REQUIRED BY SEC. R318.6 (SPECIFY SIZE AND LOCATION).
  
 16- SHEET S-5: MISSING DETAIL AND SPECS FOR LEDGER #3.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 17- ARCHITECTURAL SECTIONS AND WALL SECTIONS ARE
 MISSING THE FLASHING SPECIFICATIONS. SEC. R703.8.
  
 18- SHEET A-400 WINDOW AND DOOR SCHEDULE: UPDATE THE
 MATERIAL TYPE AND GLAZING TO MATCH PRODUCT APPROVALS
 SUBMITTED AND COORDINATE WITH SPECIFICATIONS ON THE
 ENERGY CALCULATIONS. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 ***PLEASE PROVIDE WRITTEN RESPONSE TO EACH COMMENT TO
 EXPEDITE THE REVIEW PROCESS.
  
 ***NOTE: FOR YOUR INFORMATION. HOUSE DEMOLITION PERMIT
 IS REQUIRED FOR THE DEMOLITION OF EXISTING HOUSE.
 PERMIT IS NOT ISSUED YET.
  