2013-07-03 13:11:46 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. ASSEMBLY SELECTED DOES NOT MEET DESIGN PRESSURE | | REQUIREMENTS FOR ZONES 2 AND 3. EXPOSURE D, 20' MRH | | REQUIRES -81.4, -122.5 FOR ZONE 2 AND 3 RESPECTIVELY. | | THE ASSEMBLY SELECTED HAS A LIMITATION OF -60, FBC 2010 | | RESIDENTIAL 301. | | | | 2. PROVIDE THE COMPLETE FLORIDA STATE PRODUCT APPROVAL | | INCLUDING COVER SHEET, FAC9N-3. |
|