 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE GENERAL NOTES INDICATE LIGHT HAZARD SPACING/DESIGN
 FOR OFFICE AND BATHROOMS. SEVERAL ROOMS NOT CLASSIFIED
 AS OFFICE SPACE HAVE SPRINKLER COVERAGE THAT EXCEEDS
 130 SQ.FT. INCLUCING:
 EVIDENCE STORAGE #429, TDS STORAGE #403, SUPPLIES #409,
 STORAGE #413, STORAGE #414, AND WEAPONS STORAGE #424.
  