2013-08-17 19:07:415800 SOUTH DIXIE HIGHWAY
 PERMIT #13061104
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PER NFPA 101, SECTION 8.3.2.4, EACH FIRE BARRIER SHALL
 BE PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING
 READING FIRE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER.
  
 PER NFPA 101, SECTION 8.3.5.1, PENETRATIONS THROUGH A
 FIRE-RATED WALL ASSEMBLY SHALL BE PROTECTED BY A
 FIRESTOP SYSTEM OR DEVICE.
  