2013-08-17 11:01:27BUILDING PLAN REVIEW
 PERMIT: 13061104
 ADD: 5800 S DIXIE
 CONT: MIKE MOORE
 TEL: (561)301-9468
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: AUGUST 17/2013
 ACTION: DENIED
  
 FROM 1ST REVIEW, QUESTION WAS ASKED IF THIS BUILDING IS
 FIRE SPRINKLERED, NOT PROVIDED, ASSUMED FOR THIS PLAN
 REVIEW, NON-SPRINKLERED.
  
 1) SHEET A1.1: THE CONTRACTOR WILL NEED TO UPDATE THE
 EXISSTING PERMIT APPLICATION AND APPLY FOR A SECOND
 PERMIT APPLICATION. THE PLANS INDICATE THE SPLITING OF
 A SINGLE TENANT SPACE INTO TWO INDIVUAL TENANT SPECES
 BY CREATING A TENANT SEPERATION WALL. THE CURRENT
 PERMIT APPLICATION UNDER THE DESCRIPTION OF WORK ONLY
 LIST A DEMISSING WALL. THE PLANS REFLECT ALSO THE
 CREATION OF TWO RESTROOMS, ONE IN EACH TENANT SPACE.
 NOTE THE VALLUE FOR THE NEW TENANT SEPERATION WALL, 2
 NEW RESTROOM WALLS, AND THE OUTFITTING OF RESTROOMS IS
 ONLY $1,500.00.
  
 1A) ON THE EXISTING PERMIT APPLICATION UPDATE THE
 DESCRIPTION OF WORK, ADD A SUITE NUMBER TO THE
 APPLICATION AND INCREASE THE VALUE OF WORK TO BE
 COMPLETED UNDER THIS PERMIT.
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 108.3* BUILDING PERMIT VALUATION. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER
 ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFRENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 1B) SUBMIT A SECOND PERMIT PERMIT APPLICATION UPDATE
 THE DESCRIPTION OF WORK, ADD A SUITE NUMBER TO THE
 APPLICATION AND INCREASE THE VALUE OF WORK TO BE
 COMPLETED UNDER THIS PERMIT.
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 108.3* BUILDING PERMIT VALUATION. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER
 ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFRENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 1C) NOTE INDICATES THE CHOICE OF TWO 1 HOUR UL RATINGS
 FOR THE 1 HOUR TENANT SEPERATION WALL. PLEASE SUBMIT
 ONE UL DESIGN AND PRODUCE THE DESIGN ON THE PLANS,
 INSPECTORS DO NOT CARRY A UL BOOK IN THEIR CAR.
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH
 DRAWINGS AND SPECIFICATIONS SHALL CONTAIN INFORMATION,
 IN THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 PLEASE NOTE SOME OF THE UL LISTINGS INDICATE TO TAKE
 THE WALL TO THE CEILING LINE. PLEASE REVIEW2010 FBC-B
 709.4 CONTINUITY.
 FIRE PARTITIONS SHALL EXTEND FROM THE TOP OF THE
 FOUNDATION OR FLOOR/CEILING ASSEMBLY BELOW TO THE
 UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, SLAB OR DECK
 ABOVE OR TO THE FIRE-RESISTANCE-RATED FLOOR/CEILING OR
 ROOF/CEILING ASSEMBLY ABOVE, AND SHALL BE SECURELY
 ATTACHED THERETO. IF THE PARTITIONS ARE NOT CONTINUOUS
 TO THE SHEATHING, DECK OR SLAB, AND WHERE CONSTRUCTED
 OF COMBUSTIBLE CONSTRUCTION, THE SPACE BETWEEN THE
 CEILING AND THE SHEATHING, DECK OR SLAB ABOVE SHALL BE
 FIREBLOCKED OR DRAFTSTOPPED IN ACCORDANCE WITH SECTIONS
 717.2 AND 717.3 AT THE PARTITION LINE. THE SUPPORTING
 CONSTRUCTION SHALL BE PROTECTED TO AFFORD THE REQUIRED
 FIRE-RESISTANCE RATING OF THE WALL SUPPORTED, EXCEPT
 FOR WALLS SEPARATING TENANT SPACES IN COVERED MALL
 BUILDINGS, WALLS SEPARATING DWELLING UNITS, WALLS
 SEPARATING SLEEPING UNITS AND CORRIDOR WALLS, IN
 BUILDINGS OF TYPE IIB, IIIB AND VB CONSTRUCTION.
  
 1D) THE PLANS DO NOT INDICATE WHICH WAY THE ROOF
 FRAMING MEMBERS ARE DESIGNED, IF THE ROOF FRAMING
 MEMBERS PENETRATE THE NEW 1 HOUR FIRE RATED WALL OR
 THERE IS ANY OTHER PENETRATIONS OF THE 1 HOUR RATED
 WALL COMPLIANCE WITH 2010 FBC-B 709.7 PENETRATIONS.
 PENETRATIONS OF FIRE PARTITIONS SHALL COMPLY WITH
 SECTION 713.
 713.3.1 THROUGH PENETRATIONS.
 THROUGH PENETRATIONS OF FIRE-RESISTANCE-RATED WALLS
 SHALL COMPLY WITH SECTION 713.3.1.1 OR 713.3.1.2.
 713.3.1.1 FIRE-RESISTANCE-RATED ASSEMBLIES.
 PENETRATIONS SHALL BE INSTALLED AS TESTED IN AN
 APPROVED FIRE-RESISTANCE-RATED ASSEMBLY.
  
 713.3.1.2 THROUGH-PENETRATION FIRESTOP SYSTEM.
 THROUGH PENETRATIONS SHALL BE PROTECTED BY AN APPROVED
 PENETRATION FIRESTOP SYSTEM INSTALLED AS TESTED IN
 ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A MINIMUM
 POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH (2.49 PA)
 OF WATER AND SHALL HAVE AN F RATING OF NOT LESS THAN
 THE REQUIRED FIRE-RESISTANCE RATING OF THE WALL
 PENETRATED.
  
 1E) 2010 FBC-B 713.6
 FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
 BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL
 REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: ?FIRE
 AND SMOKE BARRIER ? PROTECT ALL OPENINGS.?
  
 1F) PLEASE REVIEW PLUMBING COMMENTS ABOUT THE
 ACCESSIBLE RESTROOM THAT IS DESIGNED WITH THE OUTSIDE
 DIMENSION OF 7'-2", THE MINIMUM INTERIOR DIMENSION IS
 7'-1". 2010 FL ACC CODE FIGURE 604.8.1.6.
  
 SUGGEST A MEETING BEFORE PLANS ARE RESUBMITTED TO
 REVIEW AND MAKE SURE A PERMIT WILL BE ABLE ISSUED UNDER
 THE NEXT REVIEW!!!!
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved