2013-08-15 12:33:11 | FBC 2010 EXISTING BUILDING CODE |
| FBC 2010 ACCESSIBILITY CODE |
| FBC 2010 PLUMBING REVIEW #1 |
| DENIED: |
| |
| 1. THE NEW RESTROOM IN THE 3508 S.F. RETAIL SPACE WOULD |
| NOT MEET (IN THE SHOWN CONFIGURATION) THE 2010 |
| ACCESSIBILITY CODE. THE RESTROOM WILL BE REQUIRED TO BE |
| A MINIMUM OF 7'-1" WIDE TO ACHIEVE THE REQUIRED 60" |
| CLEAR SPACE FOR THE WATER CLOSET. (OTHER CONFIGURATIONS |
| ARE ALSO POSSIBLE). |
| FBC ACCESSIBILITY CODE 2010 604.3.1 SIZE. CLEARANCE |
| AROUND A WATER CLOSET SHALL BE 60 INCHES (1525 MM) |
| MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND |
| 56 INCHES (1420 MM) MINIMUM MEASURED PERPENDICULAR FROM |
| THE REAR WALL. |
| FBC ACCESSIBILITY CODE 2010 604.3.2 THE LAVATORY WILL |
| NOT BE PERMITTED IN THE 60" SPACE. |
| PLEASE ALSO SEE FIGURE 604.8.1.6. |
| |
| 2. BUSINESS/ MERCANTILE OCCUPANCIES WITH OVER 15 |
| OCCUPANTS REQUIRE A HIGH/LO DRINKING FOUNTAIN . |
| PLUMBING TABLE 403.1 (E) (F) |
| FBC ACCESSIBILITY CODE 2010 211.2 MINIMUM NUMBER. NO |
| FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. |
| ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH |
| 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH |
| 602.7. |
| EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES |
| WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE |
| PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING |
| FOUNTAINS. |
| |
| 3. NO PLUMBING DRAWINGS WERE FOUND WITH THIS PLAN. IF |
| THE PLUMBING CONTRACTOR IS GOING TO DO THE DRAWING AT |
| THE TIME OF APPLICATION PLEASE MAKE NOTE OF THIS WITH |
| THE NEXT SUBMITTAL. |
| |
| REVIEW BY |
| LARRY WAGNER |
| CHIEF PLUMBING INSPECTOR |
| PHONE # 805-6692 |
| EMAIL [email protected] |
| FAX # 805-6676 |
| |