2013-07-11 13:01:24 | BUILDING PLAN REVIEW |
| PERMIT: 13060989 |
| ADD: 1801 S FLAGLER DR # 802 |
| CONT:MARYJULECONSTRUCTION |
| TEL: (561)386-6032 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 1ST REVIEW |
| DATE: JULY 11/ 2013 |
| ACTION: PROVISO |
| BUILDING APPROVED WITH EXCEPTION! |
| THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1) PLANS WILL REQUIRE A DETAIL FOR THE CREATION OF A |
| NEW DROPPED CEILING AND SOFFITS. THE DETAIL SHALL |
| INCLUDE, FRAMING MATERIALS, SIZE, GAUGE, SPACING OF |
| FRAMING, SPAN OF CEILING BEING HUNG, IF STIFF BACKS ARE |
| REQUIRED? PROVIDE DETAIL OF HOW THE TRAY DROPPED CEILNG |
| WILL BE ATTACHED TO THE DECK ABOVE, TYPE OF FASTENER, |
| AND LENGTH, ALSO INCLUDE TYPE OF CEILING FINISH AND |
| THICKNESS OF MATERIAL. WILL THE DROPPED CEILING ABOVE |
| BE CONSIDERED A PLENUM? |
| 2010 WPB ADMINISTRATIVE CODE 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE |
| DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED WHEN |
| APPROVED BY THE BUILDING OFFICIAL. CONSTRUCTION |
| DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE |
| THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED |
| AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. |
| |
| 2) PLANS SHOW A KITCHEN WALL BEING MOVED, NEW FLOOR |
| AREA IS GOING TO BE REVEALED. IF THE FLOOR FINISH OF |
| THE KITCHEN IS NOT BEING REMOVED, THIS IS CONSIDERED A |
| REPAIR AND NO FLOOR INSULATION IS NEEDED. IF THE |
| KITCHEN FLOOR IS REMOVED THEN COMPLIANCE WITH THE |
| FOLLOWING SECTIONS WILL NEED TO BE REQUIRED: |
| |
| 2A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| 2B) FBC-B 2010 603.2 EXCEPTION (1) TILE FLOORING |
| FLOOR INSULATION PLACED BETWEEN TWO LAYERS OF |
| NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING |
| AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX |
| OF NOT MORE THAN 100. |
| |
| 2C) FBC-B 2010 603.2 EXCEPTION 2 WOOD FLOORS |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| FBC-B 2010 |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |