2013-06-27 14:16:45PLANS DENIED
 1) PROVIDE GRILL SIZE ON THE PLANS
 PER SECTION 107 FBC 2010
 2) REFER TO SECTION 403.5 MECHANICAL
 VENTILATION FOR FRESH AIR AND EXHAUST.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676