2013-06-26 14:06:56RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY FROM NOA
 12-0815.07 SUBMITTED IS GOING TO BE INSTALLED TO VERIFY
 COMPLIANCE WITH SEC. R301.2.1.4.3 OF 2010
 FBC-RESIDENTIAL.
  
 2- IF DESIGN PRESSURES FROM SELECTED ASSEMBLY DON'T
 MEET THE DESIGN PRESSURES FOR THE PERIMETER AND CORNER
 AREAS, THEN SIGNED AND SEALED RAS 117 CALCULATIONS ARE
 REQUIRED. SEE GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED. DESIGN PRESSURES ARE CALCULATED BASED ON
 SEC. R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL.
  