Plan Review Notes
Plan Review Notes For Permit 13060944
Permit Number 13060944
Review Stop B
Sequence Number 1
Notes
Date Text
2013-06-26 11:40:032010 FBC
  
 DENIED BY BUILDING
  
 1) THE PRODUCT APPROVAL THAT WAS SUBMITTED IS FOR A
 RECOVER DECK, WHICH MEANS THIS SYSTEM IS INSTALLED OVER
 THE EXISTING ROOFING. THE SCOPE OF WORK INDICATES THAT
 THE EXISTING ROOFING WILL BE REMOVED DOWN TO THE METAL
 DECK. PLEASE CLARIFY. CITY AMENDMENTS 107.2.1 AND DCA
 RULE 9N-3 NOTE: NOA NO. 12-1019.29 IS FOR THIS PRODUCT
 OVER STEEL DECKS.
  
 2) THIS STRUCTURE IS LOCATED IN A 170 MPH VULT WIND
 SPEED AND EXPOSURE CATEGORY C. THE MAXIMUM DESIGN
 PRESSURES FOR THE ASSEMBLY ON PAGE 30 THAT WAS
 SUBMITTED ARE TOO LOW AND CAN NOT BE INCREASED BY
 ENHANCED FASTENING. SEE LIMITATION NUMBER 9 ON PAGE 61
 OF THE NOA. FBC 1609.1
  