Plan Review Notes
Plan Review Notes For Permit 13060898
Permit Number 13060898
Review Stop B
Sequence Number 1
Notes
Date Text
2013-06-27 09:30:24****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
  
 TEST REPORT SUBMITTED INCLUDES A SUSPENDED GYPSUM
 CEILING. PROVIDE INFORMATION AS TO THIS APPLICATION,
 HOW IT HAS BEEN DETERMINED THAT THE UNIT BELOW HAS AND
 WILL ALWAYS HAVE A SUSPENDED GYPSUM CEILING.
  
 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492.
  
 TEST PROVIDED WAS ASTM E 2179. PLEASE ADDRESS.
  