Plan Review Notes For Permit 13060898 |
Permit Number |
13060898 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-06-27 09:30:24 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. | | | | TEST REPORT SUBMITTED INCLUDES A SUSPENDED GYPSUM | | CEILING. PROVIDE INFORMATION AS TO THIS APPLICATION, | | HOW IT HAS BEEN DETERMINED THAT THE UNIT BELOW HAS AND | | WILL ALWAYS HAVE A SUSPENDED GYPSUM CEILING. | | | | 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN | | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH | | ASTM E 492. | | | | TEST PROVIDED WAS ASTM E 2179. PLEASE ADDRESS. | | |
|