2013-06-25 12:28:27****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 ****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. REVISE THE FLOOR PLAN TO NOTE EXISTING CONDITIONS
 (TYPE OF WINDOW SUCH AS CASEMENT, SINGLE HUNG, ETC.)
 AND EXISTING CLEAR OPENING SIZE AND PROPOSED CLEAR
 OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB 604.1. THE
 CLEAR OPENING CANNOT BE REDUCED BY MORE THAN 5%.
  
 THE CLEAR OPENING IS THE OPENING CREATED BY THE WINDOW
 IN THE OPEN POSITION, NOT THE OVERALL WINDOW DIMENSION.
  
 2. FBC 2010 ENERGY CONSERVATION, TABLE 101.4.1, SEE
 FOOTNOTE D. PROVIDE SPECS FROM MANUFACTURER TO SHOW
 COMPLIANCE WITH FENESTRATION REQUIREMENTS.
  
  
  