Plan Review Notes For Permit 13060785 |
Permit Number |
13060785 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-07-26 16:24:21 | 2010 FBC | | | | DENIED BY MECHANICAL | | | | 1) THE MECHANICAL PLANS FOR THE SECOND FLOOR FROM CEE | | DEE A/C DO NOT COMPLY WITH FBCR M1602.4 FOR BALANCED | | RETURN AIR. TRANSFER DUCTS ARE REQUIRED TO BE 1.5 TIMES | | THE CROSS SECTIONAL AREA OF SUPPLY DUCT ENTERING THE | | ROOM OR SPACE IT IS SERVING AND THE DOOR HAVING AT | | LEAST A ONE INCH UNDERCUT. ALSO, ALL OF THE SUPPLY AIR | | ENTERING THE MASTER SUITE HAS TO BE INCLUDED IN SIZING | | THE TRANSFER DUCT FROM THAT AREA. PLEASE CORRECT | | DRAWINGS. | | | | |
|