2013-07-26 16:24:212010 FBC
  
 DENIED BY MECHANICAL
  
 1) THE MECHANICAL PLANS FOR THE SECOND FLOOR FROM CEE
 DEE A/C DO NOT COMPLY WITH FBCR M1602.4 FOR BALANCED
 RETURN AIR. TRANSFER DUCTS ARE REQUIRED TO BE 1.5 TIMES
 THE CROSS SECTIONAL AREA OF SUPPLY DUCT ENTERING THE
 ROOM OR SPACE IT IS SERVING AND THE DOOR HAVING AT
 LEAST A ONE INCH UNDERCUT. ALSO, ALL OF THE SUPPLY AIR
 ENTERING THE MASTER SUITE HAS TO BE INCLUDED IN SIZING
 THE TRANSFER DUCT FROM THAT AREA. PLEASE CORRECT
 DRAWINGS.
  
  