| 1ST REVIEW |
| DATE: JULY 22/2013 |
| ACTION: DENIED |
| PAVILION |
| |
| 1) MISSING SOILS REPORT. 2010 FBC-B 1803.6. |
| |
| 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 3) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.41 COMPONENTS & CLADDING |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(C) WALL LOUVERS, , |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| |
| 4) MISSING ON PLANS 2010 FBC-B 1209.2 ATTIC SPACES. |
| AN OPENING NOT LESS THAN 20 INCHES BY 30 INCHES (559 MM |
| BY 762 MM) SHALL BE PROVIDED TO ANY ATTIC AREA HAVING A |
| CLEAR HEIGHT OF OVER 30 INCHES (762 MM). A 30-INCH (762 |
| MM) MINIMUM CLEAR HEADROOM IN THE ATTIC SPACE SHALL BE |
| PROVIDED AT OR ABOVE THE ACCESS OPENING. |
| |
| 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |