Plan Review Notes For Permit 13060742 |
Permit Number |
13060742 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-06-21 13:03:46 | G2411.1.1 (310.1.1) CSST. | | CORRUGATED STAINLESS STEEL TUBING (CSST) GAS PIPING | | SYSTEMS SHALL BE BONDED TO THE ELECTRICAL SERVICE | | GROUNDING ELECTRODE SYSTEM AT THE POINT WHERE THE GAS | | SERVICE ENTERS THE BUILDING. THE BONDING JUMPER SHALL | | BE NOT SMALLER THAN 6 AWG COPPER WIRE OR EQUIVALENT. | | | | G2420.4 (409.4) MP REGULATOR VALVES. | | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY | | AHEAD OF EACH MP REGULATOR. |
|