Plan Review Notes For Permit 13060734 |
Permit Number |
13060734 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-06-20 13:38:10 | 2010 FBC | | | | DENIED BUILDING | | | | 1) SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES LISTED | | IN THE CERTAINTEED CORP. FLINTASTIC SA ROOFING SYSTEM ( | | NOA 10-0330.02 ) PRODUCT APPROVAL AND IT'S MAXIMUM | | DESIGN PRESSURE WILL BE USED ON THE FLAT DECK. DCA RULE | | 9N-3 AND FBC R301.2.1 | | | | 2) THE STRUCTURE IS LOCATED IN A 170 MPH VULT (132 MPH | | VALT) WIND-SPEED AND EXPOSURE CATEGORY D. FOR A | | STRUCTURE WITH A 15' MRH, THE UPLIFT PRESSURES FOR ROOF | | ZONES 2 &3 ARE - 99.0 PSF AND -116.2 PSF. THESE | | PRESSURES EXCEED THE MAXIMUM DESIGN PRESSURES IN THE | | PRODUCT APPROVAL. SUBMIT TWO COPIES OF SIGNED AND | | SEALED RAS 117 CALCULATIONS AS REQUIRED BY LIMITATION | | NUMBER 7 OF NOA 10-0330.02. FBC R 301.2.1 AND CITY | | AMENDMENTS 107.2.1.3 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|