Plan Review Notes For Permit 13060716 |
Permit Number |
13060716 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-07-10 11:17:56 | 13060716 | | 9055 IBIS BLVD. | | MODULAR BATHROOM | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | REVIEW COMMENTS. | | | | PROVIDE AN ELECTRICAL PERMIT APPLICATION WITH AN | | ELECTRICAL RISER PLAN SHOWING THE PROPOSED ELECTRICAL | | SERVICE WITH CONDUIT, MAIN DISCONNECT, SERVICE | | CONDUCTORS AND GROUNDING. NEC 110.8, 215.5 | | | | INDICATE THE FAULT CURRENT RATING OF THE EQUIPMENT. NEC | | 110.9 | | | | VERIFY THAT THE REQUIRED WORKING CLEARANCES AND | | DEDICATED WORKING SPACE HAS BEEN PROVIDED FOR THE | | ELECTRICAL EQUIPMENT AND PANEL BOARDS. NEC 110.26, | | 240.24, 408.17 | | | | ROBERT LECKY | | ELECTRICAL PLANS REVIEW | | |
|