2013-08-02 18:01:08 | REVISION SECOND BUILDING REVIEW COMMENTS. |
| CODE: 2010 FBC. |
| |
| 1- REVISE ENERGY CALCULATIONS. NEED TO SPECIFY R-30 |
| INSULATION IN THE CEILING AS REQUIRED BY TABLE 402A OF |
| ENERGY CALCULATIONS SUBMITTED. |
| |
| 2- TYPICAL WALL SECTION ON SHEET A-4: |
| A) R-30 CEILING INSULATION REQUIRED BY TABLE 402A OF |
| THE ENERGY CALCULATIONS SUBMITTED DOESN'T FIT ON 2X8 |
| WOOD JOISTS. REVISE AS REQUIRED. |
| |
| B) ORIGINAL COMMENT: "SPECIFY SIZE OF VENTILATION TO |
| COMPLY WITH SEC. R806 OF 2010 FBC-RESIDENTIAL. ***NOTE: |
| KEEP IN MIND THAT NEED CROSS VENTILATION". |
| |
| ***THIS COMMENT WAS NOT PROPERLY ADDRESSED. WALL |
| SECTION SPECIFIES 4" X 6" VENT TO MATCH EXISTING. THIS |
| DOESN'T PROVIDE CROSS VENTILATION AND VENT SPACING IS |
| NOT SPECIFIED EITHER. REVISE AS REQUIRED. |
| |
| 3- MASTER BEDROOM EGRESS WINDOW: FLOOR PLAN ON SHEET |
| A-2 SPECIFIES 52" X 60" SINGLE HUNG WINDOW, WHILE EAST |
| ELEVATION ON SHEET A-3 SPECIFIES 52"X 54" SINGLE HUNG |
| WINDOW. THERE IS A DISCREPANCY ON SIZE. REVISE AS |
| REQUIRED TO MATCH AND MAKE SURE WINDOW COMPLIES WITH |
| EGRESS SEC. R310. |
| |
| 4- ENGINEER TO USE CURRENT SEAL AS REQUIRED BY CHAPTER |
| 471 FLORIDA STATUTE. SEAL USED SAYS "CERTIFICATE". THIS |
| SEAL IS NO ALLOWED SINCE JANUARY 2006. NEED TO RE-SEAL |
| ALL DRAWINGS AND THE RAS 117 CALCULATIONS SUBMITTED. |
| |
| 5- REVISION FEES WERE ADJUSTED ACCORDING TO EACH NEW |
| SHEET SUBMITTED. OWES $339.00. THIS INCLUDES THE $30.OO |
| ADDED BY ZONING FOR THEIR REVIEW. |
| |