Plan Review Notes
Plan Review Notes For Permit 13060645
Permit Number 13060645
Review Stop B
Sequence Number 2
Notes
Date Text
2013-08-02 18:01:08REVISION SECOND BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- REVISE ENERGY CALCULATIONS. NEED TO SPECIFY R-30
 INSULATION IN THE CEILING AS REQUIRED BY TABLE 402A OF
 ENERGY CALCULATIONS SUBMITTED.
  
 2- TYPICAL WALL SECTION ON SHEET A-4:
 A) R-30 CEILING INSULATION REQUIRED BY TABLE 402A OF
 THE ENERGY CALCULATIONS SUBMITTED DOESN'T FIT ON 2X8
 WOOD JOISTS. REVISE AS REQUIRED.
  
 B) ORIGINAL COMMENT: "SPECIFY SIZE OF VENTILATION TO
 COMPLY WITH SEC. R806 OF 2010 FBC-RESIDENTIAL. ***NOTE:
 KEEP IN MIND THAT NEED CROSS VENTILATION".
  
 ***THIS COMMENT WAS NOT PROPERLY ADDRESSED. WALL
 SECTION SPECIFIES 4" X 6" VENT TO MATCH EXISTING. THIS
 DOESN'T PROVIDE CROSS VENTILATION AND VENT SPACING IS
 NOT SPECIFIED EITHER. REVISE AS REQUIRED.
  
 3- MASTER BEDROOM EGRESS WINDOW: FLOOR PLAN ON SHEET
 A-2 SPECIFIES 52" X 60" SINGLE HUNG WINDOW, WHILE EAST
 ELEVATION ON SHEET A-3 SPECIFIES 52"X 54" SINGLE HUNG
 WINDOW. THERE IS A DISCREPANCY ON SIZE. REVISE AS
 REQUIRED TO MATCH AND MAKE SURE WINDOW COMPLIES WITH
 EGRESS SEC. R310.
  
 4- ENGINEER TO USE CURRENT SEAL AS REQUIRED BY CHAPTER
 471 FLORIDA STATUTE. SEAL USED SAYS "CERTIFICATE". THIS
 SEAL IS NO ALLOWED SINCE JANUARY 2006. NEED TO RE-SEAL
 ALL DRAWINGS AND THE RAS 117 CALCULATIONS SUBMITTED.
  
 5- REVISION FEES WERE ADJUSTED ACCORDING TO EACH NEW
 SHEET SUBMITTED. OWES $339.00. THIS INCLUDES THE $30.OO
 ADDED BY ZONING FOR THEIR REVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712