2013-07-09 16:21:15RESIDENTIAL (R3) REVISION, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- REVISE ENERGY CALCULATIONS SUBMITTED: ITEM # 7(B).
 NEED R-13 MIN TO COMPLY WITH TABLE 402A ON ENERGY
 CALCULATIONS SUBMITTED.
  
 2- SHEET A-3B:
 A) SPECIFY INSULATION ON THE RAISED FLOOR. COORDINATE
 WITH ENERGY CALCULATIONS ITEM #1 ABOVE. SEC. 103.2.2 OF
 2010 FBC-ENERGY CONSERVATION.
  
 B) TYPICAL WALL SECTION:
 (1) IT'S NOT CLEAR IF EXTERIOR WALL IS 2X4 OR 2X6. WALL
 SECTION CALLS FOR 2X4 DOUBLE TOP PLATE AND 2X4 BOTTOM
 PLATE, WHILE SPECS FOR WALL CALLS FOR 2X6 WOOD STUDS
 @16"O.C. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
 (2) R-19 INSULATION SPECIFIED ON THE ENERGY
 CALCULATIONS DOESN'T FIT ON A 2X6 WALL. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
 (3) R-30 CEILING INSULATION REQUIRED BY THE ENERGY
 CALCULATIONS DOESN'T FIT ON 2X6 WOOD JOISTS. REVISE AS
 REQUIRED. ***NOTE; COORDINATE WITH ITEM #2 (B)(5)
 BELOW. SEC. 107.2.1 CITY AMENDMENTS.
 (4) ROOF SHEATHING SIZE SPECIFIED DOESN'T MATCH ROOF
 SHEATHING SPECIFIED ON THE DIAPHRAGM SCHEDULE ON SAME
 SHEET. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
 (5) SPECIFY SIZE OF VENTILATION TO COMPLY WITH SEC.
 R806 OF 2010 FBC-RESIDENTIAL. ***NOTE: KEEP IN MIND
 THAT NEED CROSS VENTILATION.
 (6) PROVIDE COMPLETE SPECIFICATIONS FOR WOOD PROTECTION
 (FLOOR JOISTS) AS REQUIRED BY SEC. R317.1.
 (7) SPECIFY 7/8" MIN. STUCCO THICKNESS AS REQUIRED BY
 TABLE R702.1(1).
 (8) SPECIFY TWO LAYERS OF APPROVED WATER RESISTANT
 BARRIER AS REQUIRED BY SEC. R703.6.3.
  
 C) SPECIFY DIMENSION "A" ON ROOF ZONES SKETCH SHOWN
 ABOVE THE DIAPHRAGM SCHEDULE. SEE NOTE "A" ON FIGURE
 R301.2(7) AND ROOF SHEATHING NAILING ZONES FIGURE
 R803.2.3.1.
  
 D) ROOF PLAN: SPECIFY MIN. ROOF PITCH OF 1/4 PER FT. AS
 REQUIRED BY SEC. R905.11.1.
  
 3- MASTER BEDROOM EGRESS WAS REDUCED WHEN CLOSING THE
 WINDOW TO ALLOW FOR THE BATHROOM ADDITION. NEED TO
 PROVIDE COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC.
 R310.
  
 4- LOW SLOPE ROOF: PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND CORNER
 AREAS AS REQUIRED BY GENERAL LIMITATION #7 TO MEET THE
 DESIGN PRESSURES OF SEC. R301.2.1.4.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712