2013-07-09 16:21:15 | RESIDENTIAL (R3) REVISION, BUILDING REVIEW COMMENTS. |
| CODE: 2010 FBC. |
| |
| 1- REVISE ENERGY CALCULATIONS SUBMITTED: ITEM # 7(B). |
| NEED R-13 MIN TO COMPLY WITH TABLE 402A ON ENERGY |
| CALCULATIONS SUBMITTED. |
| |
| 2- SHEET A-3B: |
| A) SPECIFY INSULATION ON THE RAISED FLOOR. COORDINATE |
| WITH ENERGY CALCULATIONS ITEM #1 ABOVE. SEC. 103.2.2 OF |
| 2010 FBC-ENERGY CONSERVATION. |
| |
| B) TYPICAL WALL SECTION: |
| (1) IT'S NOT CLEAR IF EXTERIOR WALL IS 2X4 OR 2X6. WALL |
| SECTION CALLS FOR 2X4 DOUBLE TOP PLATE AND 2X4 BOTTOM |
| PLATE, WHILE SPECS FOR WALL CALLS FOR 2X6 WOOD STUDS |
| @16"O.C. SEC. 107.2.1 CITY AMENDMENTS TO FBC. |
| (2) R-19 INSULATION SPECIFIED ON THE ENERGY |
| CALCULATIONS DOESN'T FIT ON A 2X6 WALL. REVISE AS |
| REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| (3) R-30 CEILING INSULATION REQUIRED BY THE ENERGY |
| CALCULATIONS DOESN'T FIT ON 2X6 WOOD JOISTS. REVISE AS |
| REQUIRED. ***NOTE; COORDINATE WITH ITEM #2 (B)(5) |
| BELOW. SEC. 107.2.1 CITY AMENDMENTS. |
| (4) ROOF SHEATHING SIZE SPECIFIED DOESN'T MATCH ROOF |
| SHEATHING SPECIFIED ON THE DIAPHRAGM SCHEDULE ON SAME |
| SHEET. REVISE AS REQUIRED. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| (5) SPECIFY SIZE OF VENTILATION TO COMPLY WITH SEC. |
| R806 OF 2010 FBC-RESIDENTIAL. ***NOTE: KEEP IN MIND |
| THAT NEED CROSS VENTILATION. |
| (6) PROVIDE COMPLETE SPECIFICATIONS FOR WOOD PROTECTION |
| (FLOOR JOISTS) AS REQUIRED BY SEC. R317.1. |
| (7) SPECIFY 7/8" MIN. STUCCO THICKNESS AS REQUIRED BY |
| TABLE R702.1(1). |
| (8) SPECIFY TWO LAYERS OF APPROVED WATER RESISTANT |
| BARRIER AS REQUIRED BY SEC. R703.6.3. |
| |
| C) SPECIFY DIMENSION "A" ON ROOF ZONES SKETCH SHOWN |
| ABOVE THE DIAPHRAGM SCHEDULE. SEE NOTE "A" ON FIGURE |
| R301.2(7) AND ROOF SHEATHING NAILING ZONES FIGURE |
| R803.2.3.1. |
| |
| D) ROOF PLAN: SPECIFY MIN. ROOF PITCH OF 1/4 PER FT. AS |
| REQUIRED BY SEC. R905.11.1. |
| |
| 3- MASTER BEDROOM EGRESS WAS REDUCED WHEN CLOSING THE |
| WINDOW TO ALLOW FOR THE BATHROOM ADDITION. NEED TO |
| PROVIDE COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. |
| R310. |
| |
| 4- LOW SLOPE ROOF: PROVIDE SIGNED AND SEALED RAS 117 |
| CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND CORNER |
| AREAS AS REQUIRED BY GENERAL LIMITATION #7 TO MEET THE |
| DESIGN PRESSURES OF SEC. R301.2.1.4.3. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561)805-6712 |