Plan Review Notes
Plan Review Notes For Permit 13060638
Permit Number 13060638
Review Stop FIRE
Sequence Number 4
Notes
Date Text
2014-04-22 15:39:52114 SOUTH OLIVE AVENUE
 PERMIT #13060638
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENTS
 SHEET FS1.1: THE PLANS ARE SEVERELY LACKING THE
 REQUIRED INFORMATION THAT SHOULD BE PROVIDED ON FIRE
 PROTECTION ENGINEERING DOCUMENTS. BELOW IS A LIST (NOT
 ALL INCLUSIVE) OF INFORMATION THAT IS INCORRECT OR
 MISSING:
 - NO WATER SUPPLY POINT OF SERVICE OR PIPE SIZES
 - NO BACKFLOW PREVENTER
 - NO UNDERGROUND WATER MAIN LOCATIONS OR SIZES
 - NO SIAMESE FIRE DEPARTMENT CONNECTION
 - NO STANDPIPE RISER SIZE
 - NO WATER SUPPLY DATA
 - NO INDICATION OF HAZARD CLASSIFICATION OR DESIGN
 DENSITY FOR SPRINKLER SYSTEM
 - NO STANDPIPE RISER OR HOSE VALVES LOCATED IN STAIR #1
 - STANDPIPE INDICATES AN ALARM CHECK VALVE?
 - NO FIRE DEPARTMENT HOSE VALVES PROVIDED ON MAIN
 LANDINGS OF 3RD FLOOR STAIRS
 - SIDEWALL SPRINKLER SHALL BE LOCATED AT THE BOTTOM OF
 THE ELEVATOR SHAFT, NOT AT THE TOP OF THE SHAFT
 - NO COMBINATION SPRINKLER/STANDPIPE RISER DIAGRAM
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730