2013-07-16 16:52:11 | BUILDING PLAN REVIEW |
| PERMIT:13060638 |
| ADD: 114 S OLIVE |
| CONT: TBD |
| TEL: (561)856-6655 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: JULY 16/2013 |
| ACTION: DENIED |
| |
| 1) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING, |
| MEETING THE DEFINITION. |
| DEFINITION: FL S. S. 553.71(7) " THRESHOLD BUILDING" |
| MEANING ANY BUILDING WHICH IS GREATER THAN (3) STORIES |
| OR 50 FT IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY |
| CLASSIFICATION AS DENIED IN THE FLORIDA BUILDING CODE |
| WHICH EXCEEDS 5,000 SQ FT IN AREA AND AN OCCUPANT |
| CONTENT OF GREATER THAN 500 PERSONS. |
| |
| 1A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A |
| SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON |
| A THRESHOLD BUILDING PURSUANT TO A WRITTEN STRUCTURAL |
| INSPECTION PLAN (THRESHOLD INSPECTION PLAN) PREPARED BY |
| THE ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN |
| MUST BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE |
| ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A |
| THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL |
| INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION |
| PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE |
| ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED |
| DOCUMENTS. |
| |
| 1B) THRESHOLD INSPECTOR: |
| WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES |
| DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL |
| INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA |
| STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS |
| CODE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL |
| INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER |
| INFORMATION |
| BEFORE THE PERMIT MAY BE ISSUED. |
| |
| 1C) THRESHOLD BLDG, REQUIRED STATEMENT: |
| W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING |
| WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S |
| KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| LOCAL AUTHORITY IN |
| ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE. |
| |
| ------------------------------------------------------- |
| ----------------------------------- |
| |
| 1D) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES |
| FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER |
| HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE |
| MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR |
| WALLS AND CEILINGS. |
| ------------------------------------------------------- |
| ------------------------------------- |
| |
| 1E) A THRESHOLD PLAN REVIEW STOP WILL BE PUT ON THIS |
| PROJECT UNTIL THESE ITEMS ARE COMPLETED AS REQUESTED BY |
| THE CHIEF BUILDING INSPECTOR KEN CONRAD: |
| |
| PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| INSPECTIONS. |
| |
| 1E)(1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN |
| CONRAD: [email protected] |
| |
| 1E)(2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A |
| RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. |
| THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| MEETING THE ABOVE CRITERIA. |
| CONTACT KEN CONRAD |
| TEL: 561-805-6666 |
| E-MAIL: [email protected] |
| |
| 2) SHEET S1.1 THE EXISTING 6 COLUMNS INDICATE TO |
| INCREASE THE LOADS ON THESE COLUMNS TO 6,000 PSF, TO |
| SEE THE GEOTECHNICAL REPORT FOR REQUIREMENTS. PLEASE |
| PROVIDE 3 SIGNED/ SEALED ORIGINAL SOILS REPORTS. 2010 |
| FBC-B 1803.3 BASIS OF INVESTIGATION. 1803.3.1 SCOPE OF |
| INVESTIGATION. THE SCOPE OF THE GEOTECHNICAL |
| INVESTIGATION INCLUDING THE NUMBER AND TYPES OF BORINGS |
| OR SOUNDINGS, THE EQUIPMENT USED TO DRILL OR SAMPLE, |
| THE IN-SITU TESTING EQUIPMENT AND THE LABORATORY |
| TESTING PROGRAM SHALL BE DETERMINED BY A REGISTERED |
| DESIGN PROFESSIONAL. |
| |
| 3) SHEET S2.1 THE WIND DESIGN CRITERIA IS GIVEN AND |
| ASSOCIATED PRESSURES, BUT THE CHART DOES NOT INDICATE |
| IF THEY ARE IN VASD OR VULT. THE OTHER ISSUE IS THE |
| CHART DOES NOT INDICATE AT WHAT SQ FT IT IS CALCULATED |
| FOR, 10 SQ FT, 20SQ FT 50 SQ FT OR 100 SQ FT? PLEASE |
| PROVIDE ADDITIONAL INFORMATION FOR REVIEW. 107.2.1.3. |
| |
| 4) PRODUCT APPROVALS: |
| 4A) 08-0125.02 EXPIRED 6/15/13 CETCO STRATASEAL |
| 4B) 08-0501.01 EXPIRED 6/19/13 AIROLITE ALUM. PENTHOUSE |
| LOUVER |
| 4C) 08-0520.04 EXPIRES 9/04/13 PLEASE UPDATE TO THE |
| NEWEST NOA |
| 4D) 11-0722.10 BILCO ROOF HATCH LOW PRESSURES AT +/- 70 |
| |
| 5) SHEET S2.1 UNDER THE WIND LOAD SCHEDULE NOTE # 1 |
| INDICATES THE USE OF THE WORD EITHER SHUTTERS OR LARGE |
| MISSILE IMPACT TESTED ... |
| 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.SUCH |
| DRAWINGS AND SPECIFICATIONS SHALL CONTAIN INFORMATION, |
| IN THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS |
| A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION. |
| |
| 6) SHEET LS 1.1, BUILDING CLASSIFICATION; |
| 6A) A-2 COMMON PATH OF TRAVEL W/ SPRINKLERS 100 FT. |
| PLEASE SEE 2010 FBC-B 1014.3 EX # 5 > 50 OCCUPANTS 20 |
| FT. |
| |
| 6B) DEAD END CORR 50 FT 1016.3 PLEASE SEE 2010 FBC-B |
| 1814 A2 ASSEMBLY 20 FT. |
| |
| 6C) TRAVEL DISTANCE 300 FT PLEASE REVIEW 2010 FBC-B |
| TABLE 1016.1 ASSEMBLY 250 FT. |
| |
| 6D) PLEASE UPDATE PLANS, THEY INDICATE A LEVEL III |
| ALTERATION THIS IS ALSO A CHANGE OF OCCUPANCY AND THE |
| 2010 EXST BLDG CODE CHANGE OF OCCUPANCY 901.3. |
| |
| 6E) OCCUPANT LOADS & EGRESS CAPACITY SEE LEVEL 3 THE |
| ERGRESS CAPACITY REQUIRED INDICATES 50 INCHES WHEREAS |
| 250 X 0.3= 75 INCHES, PLEASE CORRECT. PLEASE ALSO |
| PROVIDE ON SHEET A7.2.2 THE INSIDE CLEAR MEASUREMENT SO |
| THE EGRESS CAPACITY CAN BE CLEARLY CALULATED. |
| |
| 6F) SUBSTITUTION NOTE: 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. SUCH DRAWINGS AND |
| SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, |
| AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION. |
| |
| 7) A1.1 VERSES A7.2.1 & S1.1 A11 INDICATES A SUMP IN |
| THE ELEVATOR PIT, NONE OF THE OTHER SHEETS INDICATE |
| SUCH SUMP. 2010 FBC-B 3004.4 THE EXCEPTION ALLOWS FOR |
| SUMP PITS AND ASSOCIATED PLUMBING SUMP PUMP. PLEASE |
| PROVIDE THE MANUFACTURERS SPEC FOR THE ELEVATOR TO BE |
| IF THEY REQUIRE A SUMP, NOTE IF FIRE SPRIJNKLERS ARE |
| ACTIVATED WHERE WILL THE WATER GO WHEN ACCUMULATED IN |
| THE ELEVATOR PIT. |
| |
| 8) LS1.1, INDICATES 1 HR GLASS WALL AT STAIR # 1. ID |
| 1.2 SI-4 APPEARS TO TO FOR FWIRE GLASS DETAIL AT STAIR |
| # 1, WRONG HEADING, SI-9 DOES INDICATE THE USE OF 1 |
| HOUR FIRE RATED WIRE GLASS IN THE GLASS WALLS AND |
| DOORS. PLEASE REVIEW THE MAXIMUM AREA ALLOWED IN EXIT |
| DOORS FBC-B 715.4.4, 715.4.4.1 715.4.5 AS WELL AS TABLE |
| 715.5.4 FOR WIRE GLASS PANELS AND TABLE 715.5 FIRE |
| WINDOW ASSEMBLIES IN FIRE BARRIERS (1 HR VERTICAL |
| EXITS. |
| |
| 9) SHEET LS1.1 INDICATES THE DOORS TO STAIRWELL # 1 TO |
| BE HELD OPEN. SHEET A10.1 THE DOORS SCHEDULE TO |
| STAIRWELL 1 ( 102.01) DO NOT INDICATE HOW THEY ARE |
| GOING TO STAY OPEN OR COMPLIANCE WITH FBC-B 715.4.8. |
| DOOR CLOSING, THIS REQUIREMENT WILL NEED TO BE |
| INDICATED FOR ALL STAIRWELL DOORS. |
| |
| 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |