2013-07-16 16:52:11BUILDING PLAN REVIEW
 PERMIT:13060638
 ADD: 114 S OLIVE
 CONT: TBD
 TEL: (561)856-6655
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: JULY 16/2013
 ACTION: DENIED
  
 1) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING,
 MEETING THE DEFINITION.
 DEFINITION: FL S. S. 553.71(7) " THRESHOLD BUILDING"
 MEANING ANY BUILDING WHICH IS GREATER THAN (3) STORIES
 OR 50 FT IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DENIED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 1A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A WRITTEN STRUCTURAL
 INSPECTION PLAN (THRESHOLD INSPECTION PLAN) PREPARED BY
 THE ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE
 ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A
 THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED
 DOCUMENTS.
  
 1B) THRESHOLD INSPECTOR:
 WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER
 INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 1C) THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 -------------------------------------------------------
 -----------------------------------
  
 1D) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
 -------------------------------------------------------
 -------------------------------------
  
 1E) A THRESHOLD PLAN REVIEW STOP WILL BE PUT ON THIS
 PROJECT UNTIL THESE ITEMS ARE COMPLETED AS REQUESTED BY
 THE CHIEF BUILDING INSPECTOR KEN CONRAD:
  
 PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 1E)(1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
 THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN
 CONRAD: [email protected]
  
 1E)(2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A
 RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT.
 THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 2) SHEET S1.1 THE EXISTING 6 COLUMNS INDICATE TO
 INCREASE THE LOADS ON THESE COLUMNS TO 6,000 PSF, TO
 SEE THE GEOTECHNICAL REPORT FOR REQUIREMENTS. PLEASE
 PROVIDE 3 SIGNED/ SEALED ORIGINAL SOILS REPORTS. 2010
 FBC-B 1803.3 BASIS OF INVESTIGATION. 1803.3.1 SCOPE OF
 INVESTIGATION. THE SCOPE OF THE GEOTECHNICAL
 INVESTIGATION INCLUDING THE NUMBER AND TYPES OF BORINGS
 OR SOUNDINGS, THE EQUIPMENT USED TO DRILL OR SAMPLE,
 THE IN-SITU TESTING EQUIPMENT AND THE LABORATORY
 TESTING PROGRAM SHALL BE DETERMINED BY A REGISTERED
 DESIGN PROFESSIONAL.
  
 3) SHEET S2.1 THE WIND DESIGN CRITERIA IS GIVEN AND
 ASSOCIATED PRESSURES, BUT THE CHART DOES NOT INDICATE
 IF THEY ARE IN VASD OR VULT. THE OTHER ISSUE IS THE
 CHART DOES NOT INDICATE AT WHAT SQ FT IT IS CALCULATED
 FOR, 10 SQ FT, 20SQ FT 50 SQ FT OR 100 SQ FT? PLEASE
 PROVIDE ADDITIONAL INFORMATION FOR REVIEW. 107.2.1.3.
  
 4) PRODUCT APPROVALS:
 4A) 08-0125.02 EXPIRED 6/15/13 CETCO STRATASEAL
 4B) 08-0501.01 EXPIRED 6/19/13 AIROLITE ALUM. PENTHOUSE
 LOUVER
 4C) 08-0520.04 EXPIRES 9/04/13 PLEASE UPDATE TO THE
 NEWEST NOA
 4D) 11-0722.10 BILCO ROOF HATCH LOW PRESSURES AT +/- 70
  
 5) SHEET S2.1 UNDER THE WIND LOAD SCHEDULE NOTE # 1
 INDICATES THE USE OF THE WORD EITHER SHUTTERS OR LARGE
 MISSILE IMPACT TESTED ...
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.SUCH
 DRAWINGS AND SPECIFICATIONS SHALL CONTAIN INFORMATION,
 IN THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 6) SHEET LS 1.1, BUILDING CLASSIFICATION;
 6A) A-2 COMMON PATH OF TRAVEL W/ SPRINKLERS 100 FT.
 PLEASE SEE 2010 FBC-B 1014.3 EX # 5 > 50 OCCUPANTS 20
 FT.
  
 6B) DEAD END CORR 50 FT 1016.3 PLEASE SEE 2010 FBC-B
 1814 A2 ASSEMBLY 20 FT.
  
 6C) TRAVEL DISTANCE 300 FT PLEASE REVIEW 2010 FBC-B
 TABLE 1016.1 ASSEMBLY 250 FT.
  
 6D) PLEASE UPDATE PLANS, THEY INDICATE A LEVEL III
 ALTERATION THIS IS ALSO A CHANGE OF OCCUPANCY AND THE
 2010 EXST BLDG CODE CHANGE OF OCCUPANCY 901.3.
  
 6E) OCCUPANT LOADS & EGRESS CAPACITY SEE LEVEL 3 THE
 ERGRESS CAPACITY REQUIRED INDICATES 50 INCHES WHEREAS
 250 X 0.3= 75 INCHES, PLEASE CORRECT. PLEASE ALSO
 PROVIDE ON SHEET A7.2.2 THE INSIDE CLEAR MEASUREMENT SO
 THE EGRESS CAPACITY CAN BE CLEARLY CALULATED.
  
 6F) SUBSTITUTION NOTE: 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 7) A1.1 VERSES A7.2.1 & S1.1 A11 INDICATES A SUMP IN
 THE ELEVATOR PIT, NONE OF THE OTHER SHEETS INDICATE
 SUCH SUMP. 2010 FBC-B 3004.4 THE EXCEPTION ALLOWS FOR
 SUMP PITS AND ASSOCIATED PLUMBING SUMP PUMP. PLEASE
 PROVIDE THE MANUFACTURERS SPEC FOR THE ELEVATOR TO BE
 IF THEY REQUIRE A SUMP, NOTE IF FIRE SPRIJNKLERS ARE
 ACTIVATED WHERE WILL THE WATER GO WHEN ACCUMULATED IN
 THE ELEVATOR PIT.
  
 8) LS1.1, INDICATES 1 HR GLASS WALL AT STAIR # 1. ID
 1.2 SI-4 APPEARS TO TO FOR FWIRE GLASS DETAIL AT STAIR
 # 1, WRONG HEADING, SI-9 DOES INDICATE THE USE OF 1
 HOUR FIRE RATED WIRE GLASS IN THE GLASS WALLS AND
 DOORS. PLEASE REVIEW THE MAXIMUM AREA ALLOWED IN EXIT
 DOORS FBC-B 715.4.4, 715.4.4.1 715.4.5 AS WELL AS TABLE
 715.5.4 FOR WIRE GLASS PANELS AND TABLE 715.5 FIRE
 WINDOW ASSEMBLIES IN FIRE BARRIERS (1 HR VERTICAL
 EXITS.
  
 9) SHEET LS1.1 INDICATES THE DOORS TO STAIRWELL # 1 TO
 BE HELD OPEN. SHEET A10.1 THE DOORS SCHEDULE TO
 STAIRWELL 1 ( 102.01) DO NOT INDICATE HOW THEY ARE
 GOING TO STAY OPEN OR COMPLIANCE WITH FBC-B 715.4.8.
 DOOR CLOSING, THIS REQUIREMENT WILL NEED TO BE
 INDICATED FOR ALL STAIRWELL DOORS.
  
 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  
  
  
  
  
  
  
  