2013-07-01 14:41:38 | FBC 2010 PLUMBING REVIEW #1 |
| DENIED: |
| |
| 1. SHEET A 1.2 THE RESTROOMS HAVE 6 OR MORE REQUIRED |
| FACILITIES. THE UNISEX RESTROON MAY BE USED IN THE |
| REQUIRED FIXTURE COUNT FOR MALE OR FEMALE. |
| 403.5 UNISEX TOILET AND BATHING ROOMS. |
| IN ASSEMBLY AND MERCANTILE OCCUPANCIES, AN ACCESSIBLE |
| UNISEX TOILET ROOM SHALL BE PROVIDED WHERE AN AGGREGATE |
| OF SIX OR MORE MALE AND FEMALE WATER CLOSETS IS |
| REQUIRED. IN BUILDINGS OF MIXED OCCUPANCY, ONLY THOSE |
| WATER CLOSETS REQUIRED FOR THE ASSEMBLY OR MERCANTILE |
| OCCUPANCY SHALL BE USED TO DETERMINE THE UNISEX TOILET |
| ROOM REQUIREMENT. IN RECREATIONAL FACILITIES WHERE |
| SEPARATE-SEX BATHING ROOMS ARE PROVIDED, AN ACCESSIBLE |
| UNISEX BATHING ROOM SHALL BE PROVIDED. FIXTURES LOCATED |
| WITHIN UNISEX TOILET AND BATHING ROOMS SHALL BE |
| INCLUDED IN DETERMINING THE NUMBER OF FIXTURES PROVIDED |
| IN AN OCCUPANCY. |
| |
| 2. SHEET P 2.2 THE RAIN WATER LINES ARE NOT LABELED FOR |
| SIZE OR SQUARE FEET. |
| |
| 3. SUMP PUMPS OR FLOOR DRAINS ARE REQUIRED IN ELEVATORS |
| WITH FIREFIGHTERS' EMERGENCY OPERATION. THE DRAIN SHALL |
| BE INDIRECT TO THE SANITARY. |
| ASME A17.1 2.2.2.5 |
| P 301.6 EXCEPTION: FLOOR DRAINS, SUMPS AND SUMP PUMPS |
| SHALL BE PERMITTED AT THE BASE OF THE SHAFT, PROVIDED |
| THAT THEY ARE INDIRECTLY CONNECTED TO THE PLUMBING |
| SYSTEM AND COMPLY WITH SECTION 1003.4. |
| |
| |