Plan Review Notes For Permit 13060638 |
Permit Number |
13060638 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-07-16 13:36:39 | PLANS DENIED | | 1) IN REGARDS TO RTU ATTACHMENT TO ROOF CURB | | DETAIL. PAGE M0.1 OF PLANS REFER TO TABLE 1509.7 | | CLEARANCE BELOW RAISED ROOF MOUNTED MECHANICAL | | UNITS 2010 FBC. | | 2) SAME DETAIL PAGE M0.1 OF PLANS | | MINIMUM DESIGN WIND LOADS OF 170 MPH 2010 FBC | | 3) PROVIDE A DETAIL FROM THE ENGINEER ON THE CURB TO | | ROOF TIE DOWN PROVIDE SCREW OR BOLT SIZE PER SECTION | | 301.12 WIND RESISTANCE 2010 FBC (M) | | 4) REFER TO SECTION 503.2.4.4 SHUT OFF DAMPER CONTROLS | | FOR OUT DOOR AIR AND EXHAUST. 2010 FLORIDA ENERGY CODE | | 5) SEPARATE APPLICATION , PLANS AND PERMIT REQUIRED FOR | | HOOD AND COOLERS. | | 6) IN REGARDS TO AIR HANDLERS 1,2,3 AND 4 REFER TO | | SECTION | | 306.1 ACCESS FOR MAINTENANCE AND REPLACEMENT. 1210 | | FBC (M) | | 7) PROVIDE PRODUCT APPROVAL FOR OUT SIDE GRILLS | | AND WALL CAPS PER SECTION 107.3.4.1 2010 FBC | | 8) OUT SIDE AIR DUCT SHALL BE METAL PER DUCT BOARD | | MANUFACTURER'S ENGINEER. | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|