2013-06-26 14:50:07 | 114 SOUTH OLIVE AVENUE |
| PERMIT #13060638 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY |
| REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE |
| (2009 EDITION WITH FLORIDA AMENDMENTS.) |
| |
| GENERAL: PROVIDE DRAWING NOTE INDICATING ALL |
| CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO THE |
| REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS |
| SHALL BE REMOVED FROM THE SITE DAILY. SMOKING SHALL BE |
| PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL |
| OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE |
| RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. |
| |
| GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW |
| EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE |
| BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE |
| ORDERED FROM WWW.KNOXBOX.COM. |
| |
| SHEET LS1.1: PER SECTION 12.2.5.1.2, A DEAD-END IN AN |
| ASSEMBLY OCCUPANCY SHALL NOT EXCEED 20 FEET AND THE |
| COMMON PATH OF TRAVEL SHALL NOT EXCEED 20 FEET WHEN THE |
| PATH SERVES MORE THAN 50 OCCUPANTS. |
| |
| SHEET A7.2.1.: THE STAIR GUARDRAIL DOES NOT APPEAR TO |
| BE AT LEAST 42-INCHES TALL. |
| |
| SHEET ID1.2: DETAIL #12 (REFERENCED FROM SHEET A1.2) |
| INDICATES THE STAIR GLAZING AS NON-FIRE RATED; HOWEVER, |
| DETAIL #10 INDICATES THE GLAZING IS FIRE-RATED. |
| |
| GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT |
| DOORS WITH EXIT SIGNS. |
| |
| GENERAL: EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED |
| SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED |
| IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE |
| ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF |
| OCCUPANTS PERMITTED FOR EACH ROOM. |
| |
| SPRINKLER: PER FLORIDA ADMINISTRATIVE CODE SECTION |
| 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS |
| SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER |
| SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE |
| TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR |
| EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN |
| DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT |
| FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION |
| SUCH AS PRE-ENGINEERED SYSTEMS. |
| |
| SPRINKLER: INDICATE THE LOCATION AND DISTANCE TO THE |
| NEAREST FIRE HYDRANT. |
| |
| SPRINKLER: FOR A FULLY SPRINKLERED BUILDING, A CLASS I |
| FIRE PROTECTION STANDPIPE IS REQUIRED WHEN THE FLOOR |
| LEVEL OF THE HIGHEST STORY IS LOCATED MORE THAN 30 FEET |
| ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT VEHICHLE |
| ACCESS. |
| |
| SHEET FS1.1: ALL THE FIRE SPRINKLER FLOOR PLANS ARE |
| INDICATED AS "FIRE ALARM PLANS." |
| |
| SHEET E4.1: ALL THREE FLOOR PLANS ARE EXACTLY THE SAME. |
| |
| FIRE ALARM: PER SECTION 12.3.4.3.3, PROVIDE |
| SPEAKER/STROBE NOTIFICATION APPLIANCES AS ASSEMBLY |
| OCCUPANCIES WITH AN OCCUPANT LOAD EXCEEDING 300 |
| OCCUPANTS SHALL RECEIVE FIRE ALARM NOTIFICATION BY |
| VISIBLE SIGNALS AND VOICE ANNOUNCEMENTS. |
| |
| FIRE ALARM: PROVIDE A PRE-RECORDED FIRE ALARM |
| EVACUATION MESSAGE NOTIFYING OCCUPANTS AN EMERGENCY HAS |
| BEEN REPORTED IN THE BUILDING, LOCATE THE NEAREST EXIT, |
| AND EXIT THE BUILDING IMMEDIATELY. DO NOT USE THE |
| ELEVATOR. |
| |
| FIRE ALARM: INDICATE THE LOCATION OF THE FACP. NEW FIRE |
| ALARM SYSTEMS SHALL BE FULLY ADDRESSABLE. A CERTIFICATE |
| OF COMPLETION AND A THIRD PARTY MONITORING/VERIFICATION |
| (UL OR ETL) CERTIFICATE SHALL BE PROVIDED AT TIME OF |
| FINAL FIRE ALARM INSPECTION. PER LOCAL AHJ POLICY, DUCT |
| SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE ALARM |
| CONDITION. ELEVATOR RECALL SHALL BE INTERFACED WITH |
| FIRE ALARM SYSTEM. |
| |
| ELEVATOR: PER SECTION 9.4.3 - FIRE FIGHTERS EMERGENCY |
| OPERATIONS: ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE |
| FIGHTERS EMERGENCY OPERATIONS REQUIREMENTS OF ASME |
| A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND |
| ESCALATORS. |
| |
| WESLEY JOLIN |
| FIRE INVESTIGATOR & INSPECTOR |
| OFFICE OF THE FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |
| [email protected] |
| (561) 805-6730 |
| |