2013-07-30 14:32:25PROVIDE ARC-FLASH NOTICES AND WARNINGS PER NEC 110.16.
 PROVIDE INTERSYSTEM BONDING POINT PER 250.94. BOND ALL
 INTERIOR METAL PIPING SYSTEMS PER 250.94. PANEL B IS
 225A RATED AND PROTECTED AT 100A? LOAD IS REPRESENTED
 AS 197A ON PANEL B. SEPARATE PERMITS REQUIRED FOR FIRE
 ALARM, LOW VOLTAGE, DATA, TELEPHONE, AUDIO AND VIDEO
 SYSTEMS, ETC.