Notes |
Date |
Text |
2013-07-30 14:32:25 | PROVIDE ARC-FLASH NOTICES AND WARNINGS PER NEC 110.16. | | PROVIDE INTERSYSTEM BONDING POINT PER 250.94. BOND ALL | | INTERIOR METAL PIPING SYSTEMS PER 250.94. PANEL B IS | | 225A RATED AND PROTECTED AT 100A? LOAD IS REPRESENTED | | AS 197A ON PANEL B. SEPARATE PERMITS REQUIRED FOR FIRE | | ALARM, LOW VOLTAGE, DATA, TELEPHONE, AUDIO AND VIDEO | | SYSTEMS, ETC. |
|