2013-06-22 17:24:49313 10TH STREET
 PERMIT #13060623
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLANS AND DESIGN SHALL CONFORM TO THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 SHEET E-1: PLAN INDICATES A CARD READER ON THE EGRESS
 SIDE OF EXIT ACCESS DOOR #12. DOORS SHALL BE ARRANGED
 TO BE OPENED READILY FROM THE EGRESS SIDE WHENEVER THE
 BUILDING IS OCCUPIED. DOORS SHALL NOT REQUIRE THE USE
 OF A KEY, TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
  