Notes |
Date |
Text |
2013-07-05 09:27:31 | BUILDING APPROVED WITH EXCEPTION! | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO | | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO | | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE | | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE | | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. | | | | SHEET A-500 DETAIL # 1, CEILING INSULATION. PLEASE | | UPDATE PLANS TO COMPLY WITH 2010 FBC-B 502.3.5.2 | | UNVENTED DROPPED CEILING CAVITIES. | | WHERE UNVENTED DROPPED CEILING CAVITIES OCCUR OVER | | CONDITIONED SPACES THAT DO NOT HAVE AN AIR BARRIER | | BETWEEN THE CONDITIONED AND UNCONDITIONED SPACE (SUCH | | AS T-BAR CEILINGS), THEY SHALL BE COMPLETELY SEALED | | FROM THE EXTERIOR ENVIRONMENT (AT THE ROOF PLANE) AND | | ADJACENT SPACES BY A CONTINUOUS AIR BARRIER THAT IS | | ALSO SEALED TO THE AIR BARRIER OF THE WALLS. IN THAT | | CASE, THE ROOF ASSEMBLY SHALL CONSTITUTE BOTH THE UPPER | | THERMAL ENVELOPE AND PRESSURE ENVELOPE OF THE BUILDING. |
|