Plan Review Notes For Permit 13060550 |
Permit Number |
13060550 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-07-24 10:20:23 | 6895 NORTH JOG ROAD - SCALES | | PERMIT #13060550 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | THE EXISTING ROADWAY BYPASS (FOR THE EXISTING SCALES) | | IS A FIRE DEPARTMENT ACCESS ROAD. INSTALLATION OF A NEW | | UNATTENDED SCALE WILL ENCROACH UPON THE REQUIRED CLEAR | | WIDTH OF 20 FEET NEEDED FOR FIRE DEPARTMENT APPARATUS. | | PER SECTION 18.2.3.4.1.1 (NFPA 1), FIRE DEPARTMENT | | ACCESS ROADS SHALL HAVE A SURFACE DESIGNED TO | | ACCOMMODATE FIRE APPARATUS WEIGHING AT LEAST 32 TONS. | | ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED WIDTH OF NOT | | LESS THAN 20 FEET AND AN UNOBSTRUCTED VERTICAL | | CLEARANCE OF NOT LESS THAN 13 FEET 6 INCHES. | | | | WESLEY JOLIN | | FIRE INVESTIGATOR & INSPECTOR | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 | | |
|