2013-06-20 06:58:44 | MORSE GERIATRIC CENTER |
| 4847 FRED GLADSTONE DRIVE |
| 120 BED SKILLED NURSING REPLACEMENT |
| INSTALLATION OF ACCESS CONTROL EQUIPMENT |
| PERMIT # 13060523 |
| |
| 1. NO CUT SHEETS PROVIDED FOR EQUIPMENT THAT IS PLANNED |
| TO BE USED. THESE INCLUDE CARD READERS, SECURITY |
| CAMERA'S, AND REMOTE DOOR RELEASES. |
| |
| 2. DRAWINGS NEED TO DESCRIBE COMPLIANCE FOR DELAYED |
| EGRESS INSTALLATIONS ON ANY AND ALL EXIT DOORS. |
| INSTALLATIONS ON EXIT DOORS SHALL COMPLY WITH THE |
| FLORIDA FIRE PREVENTION CODE 2010 EDITION, THE 101 LIFE |
| SAFETY CODE, CHAPTER 7 (DELAYED EGRESS) REQUIREMENTS. |
| |
| 3. WHAT IS DPS EQUIPMENT DESCRIBED ON THE DRAWINGS. |
| |
| 4. PLEASE DESCRIBE FUNCTION OF CARD READERS. |
| |
| 5. EQUIPMENT NOTED TO BE INSTALLED IN STAIRWELL # 1 AND |
| 2. ONLY CERTAIN EQUIPMENT CAN BE INSTALLED IN |
| STAIRWELLS. PLEASE PROVIDE MORE DETAILS. |
| |
| 6. REVISIONS THAT CONTAIN THE LETTER A ARE NOT |
| IDENTIFIED IN THE PLAN REVIEW NOTES. |
| |
| 7. VALUE EXCEEDS 5,000.00 DOLLARS AND ARE NOT SIGNED |
| AND SEALED. |
| |
| 8. PLEASE INDICATE ON PLANS WHICH DOORS THAT CAN BE |
| CONSIDERED FAIL SAFE AND WHICH DOORS CAN BE IDENTIFIED |
| AS FAIL SECURE. |
| |
| 9. PLEASE INDICATE HOW THESE LOW VOLTAGE INSTALLATIONS |
| WILL NOT INTERFERE WITH ANY FIRE WALLS, SMOKE |
| COMPARTMENTS, FIRE DAMPERS, ETC. |
| |
| |
| DENIED |
| |
| |
| MICHAEL E. CARSILLO, ASSISTANT FIRE CHIEF |
| WEST PALM BEACH FIRE RESCUE |