2013-06-20 08:30:51MORSE GERIATRIC CENTER
 4847 FRED GLADSTONE DRIVE
 120 BED SKILLED NURSING REPLACEMENT
 FURNISH AND INSTALL COMPLETE (LV) NURSE CALL SYSTEM PER
 PLANS
  
 1. PLEASE PROVIDE CUT SHEETS FOR ALL EQUIPMENT PLANNED
 TO BE USED.
  
 2. PLANS MAKE REFERENCE REGARDING "WANDER MANAGEMENT"
 SYSTEM. PLEASE PROVIDE MORE DETAILS ON THIS SYSTEM AND
 HOW DOES IT FUNCTION.
  
 3. PLEASE DESCRIBE FURTHER NOTE # 3 WHICH STATES
 "COORDINATE RESIDENT DETECTION SENSORS WITH DOOR LOCK
 HARDWARE, FIRE ALARM DOOR OVERRIDE AND ELEVATOR
 CONTROLS".
  
 4. VALUE EXCEEDS $ 5000.00 DOLLARS. PLANS ARE NOT
 SIGNED AND SEALED.
  
 5. PLEASE INDICATE HOW LOW VOLTAGE NURSE CALL SYSTEMS
 WILL NOT INTERFERE WITH ANY FIRE WALLS, SMOKE
 COMPARTMENTS, FIRE DAMPERS, ETC.
  
 DENIED
  
  
 MICHAEL E. CARSILLO, ASSISTANT FIRE CHIEF
 WEST PALM BEACH FIRE RESCUE
  
  