Plan Review Notes For Permit 13060473 |
Permit Number |
13060473 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-07-26 13:21:40 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. PROVIDE INFORMATION REGARDING THE WINDOWS AND DOORS | | WHICH OPEN INTO THE PROPOSED SCREEN ENCLOSURE. PROVIDE | | A PLAN WHICH SHOWS ROOM DESIGNATIONS FOR EACH OPENING. | | IF BEDROOMS ARE AFFECTED, SHOW ALTERNATE MEANS OF | | EMERGENCY ESCAPE AND RESCUE FBC 2010 RESIDENTIAL 310. | | PROVIDE EXISTING CLEAR OPENING, PROPOSED NEW CLEAR | | OPENING. | | | | PLEASE FEEL FREE TO CONTACT ME PRIOR TO RESUBMITTAL IF | | YOU NEED ASSISTANCE. | | | | 2. PROVIDE A SITE PLAN WHICH SHOWS DISTANCE OF PROPOSED | | IMPROVEMENT TO LOT LINES, FBC 2010 RESIDENTIAL 302. | | | | 3. PLAN SHOWS SHINGLES, APPLICATION STATES "PLEXI | | ROOF." CORRELATE AND PROVIDE PRODUCT APPROVAL FOR ROOF | | COVERING FAC9N-3. | | | | 4. SEE FBC 2010 RESIDENTIAL 301; IT APPEARS THIS IS | | LOCATED IN EXPOSURE C. EITHER REVISE OR PROVIDE | | RATIONALE FOR DESIGN TO EXPOSURE B. | | |
|