2013-07-02 07:21:28 | BUILDING PLAN REVIEW |
| PERMIT: 13060375 |
| ADD: 3501 N MILITARY TRAIL |
| CONT: HEDRICK BROTHERS CONSTRUCTION |
| TEL: (561)689-8880 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: JULY 02/2013 |
| ACTION: PROVISO |
| BUILDING APPROVED WITH EXCEPTION! |
| THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| |
| REDLINED DRAWINGS: |
| |
| 1) SHEET 5 & 14A OF 18 HANDICAPPED RAMP HANDRAIL END |
| SECTIONS SHOW A RAIL NOT COMPLYING WITH 2010 FBC |
| 505.10.1 AND FIGURE 505.10.1 AND 307.2 PROTRUSION |
| LIMITS. 307.2 PROTRUSION LIMITS. |
| OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES (685 MM) |
| AND NOT MORE THAN 80 INCHES (2030 MM) ABOVE THE FINISH |
| FLOOR OR GROUND SHALL PROTRUDE 4 INCHES (100 MM) |
| MAXIMUM HORIZONTALLY INTO THE CIRCULATION PATH. |
| |
| 2) SHEET 11 OF 18 THE VIEWING PLATFORM DETAIL DOES NOT |
| DOES NOT PROVIDE THE HEIGTH REQUIREMENTS OF THE |
| GAURDRAIL 2010 FBC-B 1013.2. |
| |
| 3) SHEET 4 & 13 OF 18 DO NOT PROVIDE THE WIDTH OF THE |
| INTERMEDIATE RAMPS AS DESCRIBED IN 2010 |
| FBC-ACCESSBILITY CODE 405.7.4 CHANGE IN DIRECTION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |