Plan Review Notes
Plan Review Notes For Permit 13060366
Permit Number 13060366
Review Stop E
Sequence Number 1
Notes
Date Text
2013-06-19 10:48:3813060366
 221 CLEMATIS STREET #2A
 ACCESS CONTROL
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE THE WIRING METHOD, CABLE TYPE, WIRE SIZE, FIRE
 RATING AND CONDUIT SCHEDULE. PROVIDE A LISTING ON THE
 EQUIPMENT. NEC 110.3, 300.21, 725.136
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER