Plan Review Notes For Permit 13060319 |
Permit Number |
13060319 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2013-09-13 16:52:17 | ****PROVISO**** | | ****REVISION REQUIRED - REVISE PLAN TO SHOW | | COMPLIANCE**** | | ****ISSUED AT CONTRACTOR'S RISK**** | | | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. FBC 1004.1, OCCUPANT LOAD TO BE NOT LESS THAN TABLE | | 1004. MINIMUM OCCUPANT LOAD IS NOT CLEAR. FOR INSTANCE, | | AREA CALCS SHOW 442 SQUARE FEET LESS THAN THE TOTAL | | SQUARE FEET AREA. RECEPTION AREA DOES NOT APPEAR TO | | HAVE AN OCCUPANT LOAD, DINING AREA APPEARS TO BE | | UNDERSTATED (520 SF, WITHOUT FIXED SEATING, 15SF PER | | PERSON SHOULD BE 35, NOT 25). PLEASE REVISE. OCCUPANT | | LOAD OVER 50 WOULD BE A2, NOT M; SEE FBC CHAPTER 3. A2 | | HAS ADDITIONAL REQUIREMENTS (PANIC DEVICES) FBC | | 1008.1.10. | | | | 4. SEE FBC 2010 EXISTING BUILDING CHAPTER 9. WHAT WAS | | THE PREVIOUS OCCUPANCY OF THE TWO SPACES? IF THIS IS A | | CHANGE OF OCCUPANCY, REVISE PLAN TO SHOW COMPLIANCE. | | | | | | |
|