2013-06-07 13:12:54 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) THE PRODUCT APPROVAL THAT WAS SUBMITTED (NOA NO. | | 08--0410.09) REQUIRES RAS 117 CALCULATIONS FOR ENHANCED | | FASTENING AT THE CORNER AND PERIMETER AREAS TO BE | | PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED | | PROFESSIONAL ENGINEER, ARCHITECT OR ROOF CONSULTANT. | | SEE LIMITATION NUMBER 7 ON PAGE 38 OF THE NOA. DCA RULE | | 9N-3 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|