2013-10-11 11:17:55 | PROVISOS ADDED TO PLANS TO EXPEDITE ISSUANCE. DH | | | | | | ELECTRICAL PLANS, | | | | PROVIDE PLANS WITH THE FOLLOWING INFORMATION. | | 1) LOAD CALCULATION FOR PROPOSED USE OF OCCUPANCY. FBC | | CHAPTER 3 AND NEC ARTICLE 220. GENERAL LIGHTING LOADS | | BY OCCUPANCY IS 3.5 VA FOR OFFICE. | | 2) PROVIDE DETAILS ON EXISTING SERVICE AND SERVICE | | PANEL(S). NEC 230. | | 3) PROVIDE DETAILS ON HEIGHT OF NEW AND EXISTING | | RECEPTACLES AND SWITCHES. | | 4) ALL PATIENT CARE AREAS NEED TO COMPLY WITH THE | | WIRING METHODS OF NEC 517 PROVIDE WIRING METHOD THAT IS | | PROPOSED TO BE USED WITHIN THE PATIENT CARE AREAS. | | 5) PROVIDE PROPOSED WATER HEATER CUT SHEET. | | 6) PROVIDE TYPE OF WIRING METHOD AND DEVICES THAT WILL | | BE USED. FBC 107.3.5. | | 7) PROVIDE EXIT SIGNS AND EMERGENCY LIGHTING. FBC 1006. | | 8) PROVIDE A CLEAR AND LEGIBLE ELECTRICAL PLAN. | | | | REVIEWED BY WDS. | | | | DENIED SENT TO (A). | | CALLED THE CONTRACTOR "BRAD". |
|