 PERMIT # 13060215
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1. THE ADDRESS PROVIDED ON THE PLANS DOES NOT MATCH THE
 ADDRESS PROVIDED ON THE PERMIT APPLICATION.
 2. NORTH ORIENTATION IS INCORRECT.
 3. OCCUPANCY TYPE SHOULD REFLECT BUSINESS NOT
 HEALTHCARE.
 4. PER SECTION 8.7, ANY AREA (STORAGE) HAVING A DEGREE
 OF HAZARD GREATER THAN NORMAL TO THE GENERAL OCCUPANCY
 (BUSINESS) OF THE BUILDING, SHALL BE SEPARATED FROM
 NON-STORAGE AREAS WITH A 1-HOUR FIRE-RATED BARRIER OR
 BE PROTECTED WITH AN AUTOMATIC SPRINKLER SYSTEM. DOORS
 SHALL BE SELF CLOSING, POSITIVE LATCHING, AND
 FIRE-RATED FOR AT LEAST 45-MINUTES.
 5. PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
  