2013-06-25 12:08:33PERMIT ISSUED WITH THE FOLLOWING PROVISO:
  
 LOW VOLTAGE DATA CONDUCTORS ARE REQUIRED TO BE
 SEPARATED FROM THE POWER CONDUCTORS WITHIN A
 NONCONDUCTIVE SLEEVE. NEC 725.136 (D)(2)
  
 THE MAIN BREAKER IS LIMITED TO 80 AMPS. NEC T310.16
  