Notes
Date Text
2013-07-18 19:37:23****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE PLAN PROVIDED DOES NOT MATCH THE ARCHITECT'S
 PLAN, PLEASE REVISE FBC 107.
  
 2. PROVIDE ROOM DESIGNATION FOR EMERGENCY MEANS OF
 ESCAPE, FBC R 310.4.
  
 3. SCOPE INCREASED, PROVIDE AN UPDATED VALUATION FOR
 THIS PROJECT, LABOR AND MATERIALS. PROVIDE A COPY OF
 THE CONTRACT WITH COST BREAKDOWNS. FBC 109.
  
  