Plan Review Notes
Plan Review Notes For Permit 13060093
Permit Number 13060093
Review Stop B
Sequence Number 1
Notes
Date Text
2013-06-27 11:01:21REVISION BUILDING REVIEW COMMENTS.
 CODE: 2007 FBC.
  
 1- LANDING AT DOOR NEEDS TO BE 36" MIN. AS REQUIRED BY
 SEC. R311.4.3 OF 2007 FBC-RESIDENTIAL. DRAWINGS
 SUBMITTED SHOW 33" LANDING WIDTH. THIS DOESN'T COMPLY.
  
 2- NEED TO PROVIDE HANDRAILS FOR THE STAIRS AS REQUIRED
 BY SEC. R311.5.6 OF 2007 FBC-RESIDENTIAL.
  
 3- PROVIDE THE RISER AND TREAD DIMENSIONS TO VERIFY
 COMPLIANCE WITH THE STAIR RATIO REQUIRED BY SEC.
 R311.5.3.2 OF 2007 FBC-RESIDENTIAL. INFORMATION
 SUBMITTED IS NOT CLEAR.
  
 4- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR THE CONSTRUCTION OF THE DECK AND STAIRS. SPECIFY
 ALL FOOTINGS, POSTS, BEAMS, JOIST SIZE AND SPACING,
 CONNECTORS, ATTACHMENT TO THE WALL, AND DECK MATERIAL
 AND SPECIFICATIONS. SEC. 106.1.1 CITY AMENDMENTS TO
 FBC.
  
 5- PLANS TO PROVIDE THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC.
 106.1 CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712